Regency P121RC Horizontal Terminations, Vertical Venting with Three 3 90o Elbows, Option, H + H1

Models: P121LC P121 P121RC P131

1 48
Download 48 pages 21.81 Kb
Page 21
Image 21
Install the vent system according to the manufacturer's instructions included with the components.

INSTALLATION

Vertical Venting with Three (3) 90o Elbows

 

Option

 

V + V1

 

H + H1

 

A)

2' (610mm) Minimum

3' (914mm) Maximum

 

B)

3' (914mm) Minimum

6'

(1.86m)

Maximum

 

C)

4'

(1.22m) Minimum

9'

(2.7m) Maximum

 

 

D)

5'

(1.5m) Minimum

12' (3.6m)

Maximum

 

 

 

 

 

 

 

 

Withtheaboveoptions,maximumtotalpipelengthif37feetwithminimum of 5 feet total vertical and maximum 12 feet total horizontal.

Please note minimum 1 foot between 90o elbows is required.

Diagram 12

HORIZONTAL

TERMINATIONS

Install the vent system according to the manufacturer's instructions included with the components.

1) Set the unit in its desired location. Check

to determine if wall studs or roof rafters

are in the way when the venting system is

attached. If this is the case, you may want

ends, Diagram 1. Push the pipe sections completely together, then twist-lock one section clockwise approximately one-quarter turn, until the two sections are fully locked. The female locking lugs will not be visible from the outside, on the Black Pipe or fi ttings. They may be located by examining the inside of the female ends.

to adjust the location of the unit. Rough in

the gas.

2) Direct Vent pipe and fi ttings are designed

with special twist-lock connections to

connect the venting system to the appliance

fl ue outlet. A twist-lock appliance adaptor

is an available option that must be used in

conjunction with the Simpson Dura-Vent

Direct Vent GS system.

3) Put a bead of silicone inside the outer

section of the adapter and a bead of Mill

Pac on the inner collar. Slip the adapter

over the existing inner and outer fl ue collar

and fasten to the outer collar only with the

3 supplied screws (drilling pilot holes will

make this easier). Level the fi replace and

fasten it to the framing using nails or screws

through the nailing strips.

4) Assemble the desired combination of pipe

and elbows to the appliance adaptor and

twist-lock for a solid connection.

Note:

a)Twist-lockprocedure:Fourindentations, located on the female ends of pipes and fi ttings, are designed to slide straight onto the male ends of adjacent pipes and fi ttings, by orienting the four pipe indentations so they match and slide in to the four entry slots on the male

Diagram 1

Note: Apply sealant "Mill-Pac" to inner pipe and high temperature silicone sealant to outer pipe on every twist- lock joint.

b)Horizontal runs of vent must be supported every three feet. Wall straps are available for this purpose.

5)Mark the wall for a 10" x 10" square hole. The center of the square hole should line up with the centerline of the horizontal pipe. Cut and frame the 10 inch square hole in the exterior wall where the vent will be terminated. If the wall being penetrated is constructedofnon-combustiblematerial,i.e. masonry block or concrete, a 7"(178mm) dia. (7-1/2"(191mm) dia. for fl ex) hole is acceptable.

Note: With Dura-Vent, the minimum height is achieved by installing a 45o elbow directly to the rigid pipe adaptor.

Diagram 2

Note:

a)The horizontal run of vent must be level, or have a 1/4 inch rise for every 1 foot of run towards the termination. Never allow the vent to run downward. This could cause high temperatures and may present the possibility of a fi re.

b)The location of the horizontal vent termination on an exterior wall must meet all local and national building codes, and must not be blocked or obstructed. For External Vent Terminal Locations, see diagram in the "Exterior Vent Termination Locations" section.

6)The arrow on the vent cap should be pointing up. Insure that the 1-1/2" clearances to combustible materials are maintained (Diagram 3 in the "Venting Arrangement - Horizontal Terminations" section) Install the termination cap.

The four wood screws provided should be replaced with appropriate fasteners for stucco, brick, concrete, or other types of sidings.

Note: If installing termination on a siding covered wall, a vinyl siding standoff or furring strips must be used to ensure that the termination is not recessed into the siding.

Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace

21

Page 21
Image 21
Regency P121RC, P121LC, P131 Horizontal Terminations, Vertical Venting with Three 3 90o Elbows, Option, H + H1