INSTALLATION
P121/P121LC/P121RC/P131-NG1
System Data
For 0 to 4500 feet altitude
Burner Inlet Orifice Sizes: #31
Max. Input Rating | 40,000 Btu/h |
Min. Input Rating | 20,500 Btu/h |
|
|
Supply Pressure | min.5.0" w.c. |
|
|
Manifold Pressure |
|
(High) | 3.8"+/- 0.2"w.c. |
Log Set: Ceramic fi bre, 8 per set.
Vent System: Regency® AstrocapTM,
Regency® Direct Vent System (Flex) and
Simpson
P121/P121LC/P121RC/P131-LP1
System Data
Conversion Kit#
For 0 to 4500 feet altitude
Burner Inlet Orifice Sizes: #50
Max. Input Rating | 39,000 Btu/h |
Min. Input Rating | 20,600 Btu/h |
|
|
Supply Pressure | min.12.0" w.c. |
Manifold Pressure |
|
(High) | 11"+/- 0.2" w.c. |
Log Set: Ceramic fi bre, 8 per set.
Vent System: Regency® AstrocapTM, Regency® Direct Vent System (Flex) and Simpson
HIGH ELEVATION
This unit is approved in Canada for altitude 0 to 4500 ft. (CAN1
When using copper or fl ex connectors use only approved fi ttings. Always provide a union so that gas lines can be easily disconnected for servicing. Flare nuts for copper lines and fl ex connectors are usually considered to meet this requirement.
Important:Always check for gas leaks with a soap and water solution or gas leak detector. Do not use open flame for leak testing.
PILOT ADJUSTMENT
Periodically check the pilot flames. Correct flame pattern has three strong blue flames: 1 flowing around the thermopile, 1 around the thermocouple and 1 flowing across the burner (it does not have to be touching the burner).
Note: If you haveanincorrectflamepattern, contact your Regency® dealer for further instructions.
Incorrect flame pattern will have small, probably yellow flames, not coming into proper contact with the rear burner or thermopile or thermocouple.
Note: To properly check gas pressure, both inlet and manifold pressures should be checked using the valve pressure ports on the valve.
1)Make sure the valve is in the "OFF" position.
2)Loosen the "IN" and/or "OUT" pressure tap(s), turning counterclockwise with a 1/8" wide fl at screwdriver.
3)Attach manometer to "IN" and/or "OUT" pressure tap(s) using a 5/16" ID hose.
4)Light the pilot and turn the valve to "ON" position.
5)The pressure check should be carried out with the unit burning and the setting should be within the limits specifi ed on the safety label.
6)When fi nished reading manometer, turn off the gas valve, disconnect the hose and tighten the screw (clockwise) with a 1/8" fl at screwdriver. Note: Screw should be snug, but do not over tighten.
S.I.T. VALVE DESCRIPTION
1)Gas on/off knob
2)Manual high/low adjustment
3)Pilot Adjustment
4)Thermocouple Connection - option
5)Outlet Pressure Tap
6)Inlet Pressure Tap
7)Pilot Outlet
8)Main Gas Outlet
9)Alternative TC Connection Point
GAS LINE
INSTALLATION
The gas line can be brought through either the right, the left side or the bottom of the appliance. The gas valve is situated on the bottom of the unit.
The gas line connection may be made of rigid pipe, copper pipe or an approved flex connector. (If you are using rigid pipe, ensure that the valve can be removed for servicing.) Since some municipalities have additional local codes it is always best to consult with your local authorities and the CAN/CGA B149 installation code.
For USA installations follow local codes and/or the current National Fuel Gas Code, ANSI Z223.1.
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas supply piping system by closing its individual manual
Themanifoldpressureiscontrolledbyaregulator built into the gas control, and should be checked at the pressure test point.
Regency® | 27 |