Regency P131 High Elevation, Pilot Adjustment, Gas Line Installation, Gas Pipe Pressure Testing

Models: P121LC P121 P121RC P131

1 48
Download 48 pages 21.81 Kb
Page 27
Image 27
P121/P121LC/P121RC/P131-NG1

INSTALLATION

P121/P121LC/P121RC/P131-NG1

System Data

For 0 to 4500 feet altitude

Burner Inlet Orifice Sizes: #31

Max. Input Rating

40,000 Btu/h

Min. Input Rating

20,500 Btu/h

 

 

Supply Pressure

min.5.0" w.c.

 

 

Manifold Pressure

 

(High)

3.8"+/- 0.2"w.c.

Log Set: Ceramic fi bre, 8 per set.

Vent System: Regency® AstrocapTM,

Regency® Direct Vent System (Flex) and

Simpson Dura-Vent Direct Vent System

P121/P121LC/P121RC/P131-LP1

System Data

Conversion Kit# 730-969

For 0 to 4500 feet altitude

Burner Inlet Orifice Sizes: #50

Max. Input Rating

39,000 Btu/h

Min. Input Rating

20,600 Btu/h

 

 

Supply Pressure

min.12.0" w.c.

Manifold Pressure

 

(High)

11"+/- 0.2" w.c.

Log Set: Ceramic fi bre, 8 per set.

Vent System: Regency® AstrocapTM, Regency® Direct Vent System (Flex) and Simpson Dura-Vent Direct Vent System

HIGH ELEVATION

This unit is approved in Canada for altitude 0 to 4500 ft. (CAN1 2.17-M91).

When using copper or fl ex connectors use only approved fi ttings. Always provide a union so that gas lines can be easily disconnected for servicing. Flare nuts for copper lines and fl ex connectors are usually considered to meet this requirement.

Important:Always check for gas leaks with a soap and water solution or gas leak detector. Do not use open flame for leak testing.

PILOT ADJUSTMENT

Periodically check the pilot flames. Correct flame pattern has three strong blue flames: 1 flowing around the thermopile, 1 around the thermocouple and 1 flowing across the burner (it does not have to be touching the burner).

Note: If you haveanincorrectflamepattern, contact your Regency® dealer for further instructions.

Incorrect flame pattern will have small, probably yellow flames, not coming into proper contact with the rear burner or thermopile or thermocouple.

Note: To properly check gas pressure, both inlet and manifold pressures should be checked using the valve pressure ports on the valve.

1)Make sure the valve is in the "OFF" position.

2)Loosen the "IN" and/or "OUT" pressure tap(s), turning counterclockwise with a 1/8" wide fl at screwdriver.

3)Attach manometer to "IN" and/or "OUT" pressure tap(s) using a 5/16" ID hose.

4)Light the pilot and turn the valve to "ON" position.

5)The pressure check should be carried out with the unit burning and the setting should be within the limits specifi ed on the safety label.

6)When fi nished reading manometer, turn off the gas valve, disconnect the hose and tighten the screw (clockwise) with a 1/8" fl at screwdriver. Note: Screw should be snug, but do not over tighten.

S.I.T. VALVE DESCRIPTION

1)Gas on/off knob

2)Manual high/low adjustment

3)Pilot Adjustment

4)Thermocouple Connection - option

5)Outlet Pressure Tap

6)Inlet Pressure Tap

7)Pilot Outlet

8)Main Gas Outlet

9)Alternative TC Connection Point

GAS LINE

INSTALLATION

The gas line can be brought through either the right, the left side or the bottom of the appliance. The gas valve is situated on the bottom of the unit.

The gas line connection may be made of rigid pipe, copper pipe or an approved flex connector. (If you are using rigid pipe, ensure that the valve can be removed for servicing.) Since some municipalities have additional local codes it is always best to consult with your local authorities and the CAN/CGA B149 installation code.

For USA installations follow local codes and/or the current National Fuel Gas Code, ANSI Z223.1.

GAS PIPE PRESSURE

TESTING

The appliance must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig. (3.45 kPa). Disconnect piping from valve at pressures over 1/2 psig.

Themanifoldpressureiscontrolledbyaregulator built into the gas control, and should be checked at the pressure test point.

Regency® P121-2/P121LC-2/P121RC-2/P131-2 Zero Clearance Direct Vent Gas Fireplace

27

Page 27
Image 27
Regency P131 High Elevation, Pilot Adjustment, Gas Line Installation, Gas Pipe Pressure Testing, S.I.T. Valve Description