INSTALLATION
RIGID PIPE VENTING ARRANGEMENTS - VERTICAL TERMINATIONS
(Propane & Natural Gas)
•Vent must be supported at offsets
•Maintain clearances to combustibles as listed in the "Clearances" section.
•Firestops are required at each floor level and whenever passing through a wall.
•Must use optional rigid pipe adaptor when using rigid pipe vent systems (Part#
The
Straight Up Vertical Venting | Vertical Venting with One (1) 90o Elbow | ||
|
|
|
|
| Option | V | H |
| A) | 1' (305mm) Minimum | 2' (610mm) Maximum |
| B) | 2' (610mm) Minimum | 4' (1.22m) Maximum |
| C) | 3' (914mm) Minimum | 6' (1.86m) Maximum |
| D) | 4' (1.22m) Minimum | 8' (2.4m) Maximum |
|
| ||
| With the above options, maximum total pipe length if 37 feet | ||
| with minimum of 4 feet total vertical and maximum 8 feet total | ||
| horizontal. |
|
|
| Please note minimum 1 foot between 90o elbows is required. |
Diagram 7
Diagram 8
IMPORTANT
When installing this unit vertically, the 45o elbow when installed in conjunction with the Rigid Pipe Adaptor will pertrude past the unit
Note: A