Regency U37-LP1 Installation, Gas Connection, High Elevation, Aeration Adjustment, Embers.Embers

Models: U37-LP1 U37-NG1

1 36
Download 36 pages 8.33 Kb
Page 20
Image 20
GAS CONNECTION

INSTALLATION

GAS CONNECTION

The gas connection is a 3/8" NPT 90o elbow. The gas line can be rigid pipe or to make in- stallation easier, use a listed fl exible connector and/or copper tubing if allowed by local codes. Since some municipalities have additional local codes it is always best to consult with your local authorities and the CAN/CGA B149 installation codes. For USA installations follow local codes and/or the current National Fuel Gas Code, ANSI Z223.1.

When using copper or fl ex connectors use only approved fi ttings. Always provide a union so that gas lines can be easily disconnected for burner and/or valve servicing. Flare nuts for copper lines and fl ex connectors are usually considered to meet this requirement.

Important:Always check for gas leaks with a soapandwatersolutionorgasleakdetector. Do not use open flame for leak testing.

Note: Prior to any pressure testing of the gas supply piping system that exceeds test pressures of 1/2 psig, this appliance must be disconnected from the piping system. Iftestpressuresequalto orlessthan1/2psigareusedthen this appliance must be isolated from the piping system by clos- ingitsindividualmanualshut-off valve during the testing.

System Data - U37

For 0 to 4500 feet altitude

Burner Inlet Orifice Sizes:

Natural Gas Propane

 

Burner

#37

#52

 

 

 

 

 

 

Max. Input Rating

30,000 Btu/h

 

 

Min. Input Rating

15,000 Btu/h

 

 

 

 

 

 

 

Supply Pressure

 

 

 

 

Natural Gas

min. 5.0" w.c.

 

 

Propane

min. 12.0" w.c.

 

 

 

 

 

 

 

Manifold Pressure

 

 

 

 

Natural Gas

3.8"

+/- 0.2" w.c.

 

 

Propane

11"

+/- 0.2" w.c.

 

HIGH ELEVATION

This unit is approved in Canada for altitude 0 ft. to 4500 ft. (CAN/CGA-2.17-M91). For Natural Gas installations above 4500 ft. follow current CAN/CGA-B149.1.

AERATION

ADJUSTMENT

The burner aeration is factory set but may need adjusting due to either the local gas supply, air supply or altitude.

Natural Gas:

1/4" open

Propane:

3/8" open

The aeration adjustment gears are located on the right side of the burner box and can be ac- cessed from the side or from the front when the louvers are removed.

To adjust the aeration: use the allen key to turn the turning gear which will adjust the air shutter. Open the air shutter for a blue fl ame or close it for a yellower fl ame. The factory setting should be sufficient for most installations.

Clockwise to open,

counter-clockwise to close.

Caution: Carbon will be produced if the air shutter is closed too much.

Note: Any damage due to carboning result- ing from improperly setting the aera- tion controls is NOT covered under warranty.

Note: Aeration Adjustment should only be performedbyanauthorizedRegency® Installer at the time of installation or service.

LOG SET

INSTALLATION

Read the instructions below carefully and refer to the diagrams. If logs are broken do not use the unit until they are replaced. Broken logs can interfere with the pilot operation.

The gas log kit contains the following:

a)02-65 Rear Log

b)02-56 Middle Left Log

c)02-44 Front Left Log

d)02-46 Left Top Log

e)02-45 Front Right Log

f)02-47 Center Log

g)02-48 Middle Right Log

h)

Embers

902-151

i)

Lava

902-154

The "02" refer numbers (i.e. 02-65) are

molded into the rear of each log.

1)Carefully remove the logs from the box and unwrap them. The logs are fragile, handle with care - do not force into position.

2)Sprinkle the embers on the left and right sides of the fi rebox base.

Embers.Embers

20

U37-1 Regency® ULTIMATE Rear Vent Direct Vent Freestanding Gas Stove

Page 20
Image 20
Regency U37-LP1, U37-NG1 Gas Connection, High Elevation, Aeration Adjustment, Log Set Installation, Embers.Embers