Roberts Gorden HE-60 Installation Code and Annual Inspections, Maintenance Checklist, Objects

Models: HE-125 HE-150 HE-100 HE-40 HE-175 HE-80 HE-60

1 72
Download 72 pages 53.49 Kb
Page 56
Image 56

HE-SERIES INSTALLATION, OPERATION AND SERVICE MANUAL

ation of the heating system, service and annual

Installation Code and Annual Inspections:

inspections must be done by a contractor qualified in

All installation and service of ROBERTS GORDON®

the installation and service of gas-fired heating

equipment must be performed by a contractor

equipment.

 

qualified in the installation and service of equipment

Turn off gas and electric supplies before performing

sold and supplied by Roberts-Gordon LLC and

conform to all requirements set forth in the

service or maintenance. Allow heater to cool before

ROBERTS GORDON® manuals and all applicable

servicing.

 

 

governmental authorities pertaining to the

Before every heating season, a contractor qualified in

installation, service, operation and labeling of the

the installation and service of gas-fired heating

equipment.

equipment must perform a thorough safety inspec-

To help facilitate optimum performance and safety,

tion of the heater.

 

 

Roberts-Gordon LLC recommends that a qualified

For best performance, the gas, electrical, thermostat

contractor conduct, at a minimum, annual inspec-

connections, tubing, venting, suspensions and over-

tions of your ROBERTS GORDON® equipment and

all heater condition should be thoroughly inspected.

perform service where necessary, using only

NOTE: Gas flow and burner ignition are among the

replacement parts sold and supplied by Roberts-

first things that should be inspected.

Gordon LLC.

Please see Page 50, Section 11.5 for suggested

 

items to inspect.

 

 

11.5 Maintenance Checklist

 

 

 

 

The Vicinity of the Heater

Do not store or use flammable objects, liquids or vapors near the heater.

 

Immediately remove these items if they are present. See Page 6, Section 3.

 

 

Vehicles and Other

Maintain the clearances to combustibles.

Objects

Do not hang anything from, or place anything on, the heater.

 

 

Make sure nothing is lodged underneath the reflector, in between the tubes or

 

in the decorative or protective grilles (included with select models).

 

Immediately remove objects in violation of the clearances to combustibles.

 

See Page 6, Section 3.

 

 

 

Reflector

Support reflector with reflector hanger and support strap.

 

Reflector must not touch tube.

 

Make sure there is no dirt, sagging, cracking or distortion.

 

Do not operate if there is sagging, cracking or distortion.

 

Make sure reflectors are correctly overlapped. See Page 24, Section 6.6.1.

 

Clean any debris from top and surface of reflectors with a damp cloth.

 

Check for evidence of animals such as squirrels or birds and remove any

 

nests prior to firing.

 

 

 

Vent Pipe

Venting must be intact. Using a flashlight, look for obstructions, cracks on the

 

pipe, gaps in the sealed areas or corrosion.

 

The area must be free of dirt and dust.

 

Remove any carbon deposits or scale using a wire brush.

 

Check for evidence of animals such as squirrels or birds and remove any

 

nests prior to firing. See Page 35, Section 8.

 

 

Outside Air Inlet

Inlet must be intact. Look for obstructions, cracks on the pipe, gaps in the

 

sealed areas or corrosion.

The area must be free of dirt and dust. Clean and reinstall as required.

50

Page 56
Image 56
Roberts Gorden HE-60 Installation Code and Annual Inspections, Please see Page 50, .5 for suggested, Maintenance Checklist