SECTION 11: OPERATION AND MAINTENANCE

Reflector Support Straps

Verify that the reflector support straps are securely clamped to tube and

 

reflector. See Page 24, Step 6.6.1.

 

Verify tight and loose screws at reflector overlaps.

 

 

 

Tubes

Make sure there are no cracks.

 

Make sure tubes are connected and suspended securely.

 

See Page 15, Section 6.

 

Make sure there is no sagging, bending or distortion.

 

Clean any debris from top of tubes or replace as required.

 

Check the inside of the firing tube with a flashlight. If carbon or scale are pres-

 

ent remove the turbulator(s). Scrape out the deposits with a wire brush or rod,

 

or metal plate attached to a wooden pole and replace turbulator(s) in tube.

 

Check for evidence of animals such as squirrels or birds and remove any

 

nests prior to firing.

 

 

 

Gas Line

Check for gas leaks. See Page 43, Section 9.

 

 

 

Burner Observation

Make sure it is clean and free of cracks or holes.

Window

Clean and replace as required.

 

 

 

 

Drain Hole

Be sure that the drain hole in the bottom of the burner compartment is not

 

blocked or clogged.

 

 

 

Blower Scroll, Wheel and

Compressed air or a vacuum cleaner may be used to clean dust and dirt.

Motor

 

 

 

 

 

Burner Cup and Orifice

Clear of obstructions (even spider webs will cause problems).

 

Carefully remove any dust and debris from the burner.

 

 

 

Hot-Surface Igniter

Replace if cracked or broken.

 

 

 

Thermostat

There should be no exposed wire or damage to the thermostat.

 

See Page 45, Section 10.

 

 

 

Suspension Points

Make sure the heater is hanging securely. Look for signs of wear on the chain

 

or ceiling.

 

See Page 16, Figure 14.

 

 

 

Decorative and Protective

The grille must be securely attached.

Grille (optional)

Check that the side reflector extensions are installed correctly and secured in

 

 

place if necessary (Decorative grille only).

 

See Page 32, Section 7.5 and Page 34, Section 7.6

 

Make sure shield is installed correctly and secured in place if necessary.

 

(Decorative grille only.) See Page 33, Section 7.5.2.

 

 

 

Lower Clearance Shield

The lower shield must be securely attached. Inspect shield support straps

(optional)

and lower clearance shield anchor points. See Page 32, Section 7.4.

 

Make sure shield is installed correctly and secured in place if necessary.

 

See Page 32, Section 7.4.

 

 

 

Wall Tag

If wall tag is present, make sure it is legible and accurate. Please contact

 

Roberts-Gordon LLC or your ROBERTS GORDON® independent distributor,

 

if you need a wall tag. See Page 4, Section 2.1.

 

 

 

Safety Labels

Product safety signs or labels should be replaced by the product user when

 

they are no longer legible. Please contact Roberts-Gordon LLC or your ROB-

 

ERTS GORDON® independent distributor to obtain replacement signs or

 

labels. See Page 1, Figure through Page 3, Figure 2.

 

 

 