PREPARING FOR INSTALLATION
Choosing the Installation Location
Indoor Unit
Where airflow is not blocked
Where cool air can be distributed throughout the room
Install the refrigerant piping length and the height difference of both indoor and outdoor units as indicated in the installation diagram
Wall that prevents vibration and is strong enough to hold the product weight
Out of the direct sunlight
1m or more away from the TV or radio (to prevent the screen from being distorted or noise from being generated)
As far away as possible from the fluorescent and incandescent lights (so that the remote control can be operated well)
A place where the air filter can be replaced easily
CAUTION
Outdoor Unit
Where it is not exposed to strong wind
Well ventilated and dustless places
Out of the direct sunlight and rain
Where neighbors are not annoyed by operation sound or hot air
Solid wall or support that prevents vibration and is strong enough to hold the product weight
Where there is no risk of flammable gas leakage
When installing the unit at a high place be sure to fix the unit legs
3m or more away from the TV or radio (to prevent the screen from being distorted or noise from being generated)
Install the unit horizontally
Place where drained water does not become any problem.
Place with no plants (especially climbing plants) and where small animal can not access.
ENGLISH
Avoid the following places to prevent malfunction of the unit
- Where there is machine oil | - Salty environment such as seaside areas |
- Where sulfide gas exists | - Other special atmosphere areas |
Observe the clearances and maximum lengths as seen in the picture below when installing the air conditioner.
125mm or more
Wrap the refrigerant pipes and the drain hose with the absorbent pad and vinyl tape. Refer to page 19 for further details.
300mm or more
125mm or more
You can select the direction of draining (left or right).
600mm minimum
300mm minimum
600mm minimum
CAUTION:
'L' m as maximum pipe length and 3 m as minimum pipe length (It will reduce noise and vibration)
'L ' meters maximum total pipe length
300mm minimum
'H ' meters maximum total pipe length
Model | L | H |
09 | 15 | 7 |
12 | 15 | 7 |
18 | 15 | 7 |
24 | 20 | 8 |
Make at least one round:
It will reduce noise and vibration
The appearance of the unit may be different from the diagram | |
depending on the model. |
|