Samsung AQ24UGAN, AQ09UGDN manual Cutting or Extending the Pipe, Depth a Flaring Size B

Models: AQ24UGAN AQ09UGDN

1 25
Download 25 pages 27.08 Kb
Page 14
Image 14

INSTALLING THE AIR CONDTIONER

Cutting or Extending the Pipe

A 5-meter pipe is supplied with the air conditioner (optional NOT FOR ITALY).

The length of the pipe can be:

Extended up to : see table page 5

Shorten up to: see page 5

CAUTION If you need a pipe longer than 5 meters: You must extend the assembly cable.

You must add refrigerant to the pipes; otherwise, the indoor unit may freeze.

1Make sure that you have all the required tools (pipe cutter, reamer, flaring tool and pipe holder).

Pipe cutter

Pipe

2If you want to shorten the pipe, cut it using a pipe cutter, ensuring that the cut edge remains at 90° with the side of the pipe (see below examples of correct and incorrect cut edges).

ObliqueRoughBurr

3To prevent a gas leak, remove all burrs at the cut edge of the pipe using a reamer.

CAUTION Face the pipe down while removing the burrs to make sure that burrs do not get in to the pipe.

Pipe Flare

Flare nut

 

 

 

 

 

 

 

 

 

Indoor

 

outlet pipe

 

 

Connecting pipe

 

 

4Put a flare nut slightly into the pipe and modify the flare.

Outer Diameter (D)

Depth (A)

Flaring Size (B)

ø6.35 mm

1.3 mm

9.0 mm

ø9.52 mm

1.8 mm

13.0 mm

ø12.70 mm

2.0 mm

16.2 mm

ø15.88 mm

2.2 mm

19.3 mm

ø19.05 mm

2.2 mm

22.5 mm

ø22.23 mm

2.2 mm

25.7 mm

5Check if you flared the pipe correctly (see examples of incorrectly flared pipes below).

Correct

Inclined

Damaged

Cracked

Uneven

 

 

Surface

 

Thickness

6Align the pipes to connect them easily. Tighten the flare nuts first with your hands, and then with a torque wrench, applying the following torque:

Outer Diameter

Torque (kgf•cm)

ø6.35 mm

140~170

ø9.52 mm

250~280

ø12.70 mm

380~420

ø15.88 mm

440~480

ø19.05 mm

990~1210

ø22.23 mm

990~1210

Note Excessive torque can be cause of gas leakage.

In case brazing the pipe, the nitrogen gas must be blown into the pipe (50 Pa). The joint must be accessible and serviceable.

E-14

7For further details on how to connect to the outdoor unit and purge the air, refer to page 18.

CAUTION

Tighten the flare nut with torque wrench according to specified method.

If the flare nut is over-tightened, the flare may break and cause refrigerant gas leakage.

Vivaldi_IM_30271A_E_11.07.09.indd 14

2009-11-7 13:57:05

Page 14
Image 14
Samsung AQ24UGAN, AQ09UGDN manual Cutting or Extending the Pipe, Depth a Flaring Size B