4. Service procedures
1
2
3
4
Section
– 60 – SM830076
(4) LED Indication on the Outdoor Unit’s P.C.B. Ass’yIf something goes wrong with the outdoor unit, LED lamps on the outdoor P.C.B. Ass’y lightup to show the cause of the trouble, in addition to the Alarm message on the remotecontroller.
LED 2 on
P.C. board Remote
controller
LED 1 on
P.C. board Possible cause of trouble
Normal
Outdoor unit serial communication signal is abnormal.
Outdoor unit address is duplicated.
Other outdoor units are performing auto address and
detecting refrigerant shortage.
FMo • CM thermal protection is in operation.
Power supply voltage is abnormal.
High voltage SW activates
Negative phase protector activates.
Sensor is abnormal. (Open or short)
Abnormal compressor current value is detected.
Auto address failure
Auto address is in operation.
NOTE v: LED lamps OFF V: LED lamps ON (lights up) *: LED lamps ON (flashes)
vvNo message
vV
E06, E07, L04
v*No message
VvP02
VVP04, P05
V*F04~F09
*vH01, H02
**E15, E16
**
“SETTING”
flashes.
Flash at the same time

* REFRIGERANT SHORTAGE

Note particularly that a shortage of refrigerant is only shown by the outdoor P.C.B. Ass’y

LEDs and the Alarm Message does not appear on the Indoor Remote Controller . The

compressor keeps running even when the refrigerant is less, so when you find the LED

indication on the outdoor P.C.B. Ass’y, stop the air conditioner immediately to avoid the

compressor damage.

Fig. 20

1125_C_I
LED 1 (D11)
LED 2 (D12)
CAUTION
Flash alternately