4. Service procedures
1
2
3
4
Section
– 86 – SM830076
(J) Change the period of the filter timer
If the period of filter timer is not suitable (for example in case of dirty environment), the
period can be shortened to half as follows:
aPress the TEST / CHK button for more than 4 seconds.
SET CL
MODE
FAN SPEED
ON
OFF
SET TEMP.
UNIT
FLAP
AIR FLOW
R.C. No.
SET
UNITNo.
No.CODE
TIMER SET
DATA
SETTING
TEST / CHK
0213_M_I
bIn case of group control, if you want to change all units in group control collectively,
proceed next step remaining “ALL” displayed.
If you want to change a unit individually, select the indoor unit address (UNIT No.) with
UNIT button.
cSelect the CODE No. 02 with , (SET TEMP) button.
dChange the No. from 0 to 1 with , ( ) button.
ePress the SET button.
CODE No. 06, SET DATA and
SETTING
change from flashing to ON state.
fIf you made a mistake, press the CL button.
gFinally, press the TEST / CHK button.
SET CL
MODE
FAN SPEED
ON
OFF
SET TEMP.
UNIT
FLAP
AIR FLOW
R.C. No.
SET
UNITNo.
No.CODE
SETTEMP.
TIMER SET
DATA
SETTING
TEST / CHK
0214_M_
I
EX:
UNIT No. 1–6
CODE No. 02
K type 150 hr
75 hr