Sanyo XMHS0972 Protective Functions, Overload prevention during heating, Freeze prevention

Models: XMHS1272 XMHS0972

1 105
Download 105 pages 61.32 Kb
Page 30
Image 30
7-2. Protective Functions

7-2. Protective Functions

 Overload prevention during heating Overload prevention during heating

During HEAT operation, the temperature of the indoor heat exchanger is used to control the frequency and lessen the load on the compressor before the protective device is activated.

exchanger

Approx.

 

 

 

Indoor heat exchanger

(53)

 

 

 

B. Control end

°F(°C)

 

A

 

temperature

127

 

 

A. Control start

Approx.

 

 

 

 

heat

 

 

 

B

117

 

 

 

Indoor

(47)

 

 

 

 

 

a

b

c

d

a.Area: Automatic capacity control

b.When Point A has been exceeded, the operation frequency is reduced by a certain proportion.

c.Area: Frequency increase is prohibited.

d.At Point B and below, overload prevention is ended and control is the same as in the a area.

 Cold-air prevention during heating Cold-air prevention during heating

During heating, the fan speed is set to "LL" (very low) or stopped. As the temperature of the indoor heat exchanger rises, the fan speed is changed to the set speed.

High

 

 

Set fan speed

At stability of operation

 

 

 

 

 

 

At start of operation

LL

 

 

 

Stopped

77

86

Approx. 104

 

 

(25)

(30)

(40)

Indoor heat exchanger

NOTE

temperature °F(°C)

 Freeze prevention Freeze prevention

During COOL or DRY operation, freezing is detected and operation is stopped when the temperature of the indoor heat exchanger matches the conditions below.

1.Freeze-prevention operation is engaged when the temperature of the indoor heat exchanger is below 43°F(6°C).

2.Restart after freeze-prevention operation occurs when the temperature of the indoor heat exchanger reaches 46°F(8°C) or above.

exchanger

46

 

 

 

C

 

 

 

 

 

°F(°C)

(8)

 

A

B

 

 

 

 

temperature

43

 

 

(6)

 

 

 

 

heat

36

 

 

 

 

Indoor

*

 

 

 

(2)

 

 

 

 

 

 

 

 

 

 

a

b

c

d

a.Area: Automatic capacity control

b.When the temperature drops below Point A, the operation frequency is reduced by a certain proportion.

c.Area: Frequency increase is prohibited.

d.When the temperature reaches Point C or above, freezing prevention is ended and control is the same as in the a area.

*When the temperature drops to below 36°F(2°C) (continuously for 2 minutes or longer), the compressor stops. Once the freeze condition is detected, the air conditioner will work less than the maximum frequency until it is turned off.

The fan speed is forcibly changed to "LL" beginning 30 seconds after the thermostat turns OFF.

At stability of operation refers to operation when the room temperature has approached the set temperature.

When HEAT operation starts, the indoor fan is stopped until the temperature of the indoor heat exchanger reaches 68°F(20°C) or higher, or until the room temperature reaches 59°F(15°C) or higher.