Sanyo XMHS0972, XMHS1272 Table, Embedding the Tubing and Wiring, Max. Allowable Total, Limit of

Models: XMHS1272 XMHS0972

1 105
Download 105 pages 61.32 Kb
Page 78
Image 78

Install the indoor unit more than 3.3' (1 m) away from any antenna or power lines or connecting wires used for tele- vision, radio, telephone, security system, or intercom.

Electrical noise from any of these sources may affect operation.

install in a sturdy manner to avoid increased operating noise.

Table 3

 

Max.

Max. Allowable Total

 

Limit of

Limit of Elevation

Required Amount

 

Allowable

Tubing Length

Total Tubing Length

Difference

of Additional

Model

Tubing Length

at shipment

(L1+L2+L3) or

(H1, H2, H3, H4)

Refrigerant

 

per unit

(L1+L2+L3) or

(L1+L2+L3+L4)

(ft.)

(oz./ft.)*

 

(ft.)

(L1+L2+L3+L4)

 

(ft.)

 

 

 

 

 

(ft.)

 

 

 

 

 

 

 

 

 

 

 

 

CMH1972

82

150

(L1+L2+L3)

150

(L1+L2+L3)

50

 

 

 

 

 

 

 

 

CMH2472

82

150

(L1+L2+L3+L4)

200

(L1+L2+L3+L4)

50

0.22

 

 

 

 

 

 

 

 

CMH3172

100

150

(L1+L2+L3+L4)

230

(L1+L2+L3+L4)

50

0.22

 

 

 

 

 

 

 

 

*If total tubing length becomes 150 to 200 ft. (Max.) or 150 to 230 ft. (Max.), charge additional refrigerant (R410A) by 0.22 oz./ft.

No additional charge of compressor oil is necessary. For more detailed charging information, refer to the Technical & Service Manual.

2-2. Embedding the Tubing and Wiring

Before beginning embedding installation work, consult fully with agencies or offices related to the building’s foundation, construction, electricity, and water.

Wait to make connections to the embedded portion. Each connection step is described later in this manual.

Securely cover the end of the embedded tubing to prevent intrusion of dirt or moisture.

If an embedded tube is to be left for a long time, fill the tube with nitrogen and seal both ends securely. If a tube is left open for an extended time, moisture in the air inside the tubing may condense into water droplets, and lead to water contamination of the refrig- erant circuit.

In order to prevent insulation breakdown and ground faults, do not allow wiring ends to come in contact with rainwater, or be subjected to condensation or dew.

Apply sufficient thermal insulation to the refrigerant tubing and drain pipes.

5

Page 78
Image 78
Sanyo XMHS0972 Table, Embedding the Tubing and Wiring, Max. Allowable Total, Limit of Elevation, Required Amount