Applications
Basic Operation
The Siemens BACnet Heat Pump
Control Temperature Setpoints
The controller maintains a specified temperature setpoint based on Day/Night mode, the heating/cooling mode, and the setpoint dial (if used).
Day/Night Mode
The controller maintains the specified day setpoint temperature during daytime hours and the specified night setpoint at night.
Night Mode Override Switch
If the RTS has an override switch, it can be used to command the controller into day mode for an adjustable period of time. This only affects a controller in night mode.
Control Loops
Heating Loop – maintains room temperature setpoint by turning compressors and electric heat stages on and off.
Cooling Loop – maintains room temperature setpoint by turning compressors on and off and using free cooling (mixed air control) when available.
Mixed Air Control Loop
The heat pump is controlled by three Proportional, Integral, and Derivative (PID) control loops; a cooling loop and a heating loop. This section describes the mixed air control loop.