Siemens BACnet Heat Pump Controller -
Application 2583: Multiple Compressor Heat Pump with Reversing Valve Control and Mixed Air Control
In Application 2583 (Figure 5), the controller controls a
Compressor Staging
Three compressors or electric heat stages are available for use. Each compressor has a time delay (at least 30 seconds) to lessen the demand of having more than one compressor stage start at once.
Reversing Valve Operation
The reversing valve determines the operation of the heat pump's compressors (heating or cooling) depending on the demand.
Application Notes
1.If the heat pump cycles excessively, temperature swings in the room are excessive, or there is trouble maintaining the setpoint, the cooling loop, the heating loop, or both need to be tuned. Contact your local Siemens Building Technologies representative for more information.
2.The Heat Pump
3.Running the mixed air loop during night mode can increase energy savings by taking advantage of free cooling at night to
A field panel program can be written to