Image 27
Point Database

Point Database

Description

Address

Application

Description

 

 

 

 

RM STPT MlN

11

2583, 2584

Minimum temperature setpoint in degrees that the controller

 

 

 

can use from the setpoint dial. This overrides any

 

 

 

temperature setpoint from the setpoint dial that falls below

 

 

 

this minimum.

 

 

 

Valid entry range: 48° to 95°F (9° to 35°C)

 

 

 

 

RM STPT MAX

12

2583, 2584

Maximum temperature setpoint in degrees that the controller

 

 

 

can use from the setpoint dial. This overrides any

 

 

 

temperature setpoint from the setpoint dial that raises above

 

 

 

this maximum.

 

 

 

Valid entry range: 48° to 95°F (9° to 35°C)

 

 

 

 

RM STPT DIAL

{13}

2583, 2584, 2590

Temperature setpoint in degrees from the room temperature

 

 

 

sensor (not available on all temperature sensor models).

 

 

 

This setpoint will be used for control in day mode (heating or

 

 

 

cooling) when enabled by STPT DIAL (Point 14).

 

 

 

Valid entry range: 48° to 95°F (9° to 35°C)

 

 

 

 

STPT DIAL

14

2583, 2584

YES indicates that there is a room setpoint dial on the room

 

 

 

temperature sensor and must be used as the temperature

 

 

 

setpoint for control in day/occupied mode. NO indicates that

 

 

 

the appropriate preset setpoint will be used as the

 

 

 

temperature setpoint for control in day/occupied heating or

 

 

 

cooling mode.

 

 

 

Valid input: YES or NO

 

 

 

 

AUX TEMP

{15}

2590

Actual reading from a 10K Ω thermistor connected to the

 

 

 

controller's AI 5 input. When a thermistor is connected at

 

 

 

Al 5, DI 5 is not available. See DI 5. The physical input can

 

 

 

not be used for both analog and digital input at the same

 

 

 

time.

MA TEMP

{15}

2583, 2584

Actual reading from a 10K Ω thermistor connected to the

 

 

 

controller's Al 5 input. When a thermistor is connected at

 

 

 

Al 5, DI 5 is not available. See DI 5. The physical input can

 

 

 

not be used for both analog and digital input at the same

 

 

 

time.

 

 

 

 

CMP2 ON

16

2583

Value, in percent, that the active temperature control loop

 

 

 

output must exceed for compressor 2 to turn ON. Actual

 

 

 

turn on is subject to the CMP2 MlN OFF time being expired.

HTG CMP2 ON

16

2584

Value, in percent, that the heating control loop output must

 

 

 

exceed for compressor 2 to turn ON. Actual turn on is

 

 

 

subject to the CMP2 MlN OFF time being expired.

 

 

 

 

CMP2 OFF

17

2583

Value, in percent, that the active temperature control loop

 

 

 

output must go below for compressor 2 to turn OFF. Actual

 

 

 

turn off is subject to the CMP2 MlN ON time being expired.

HTG CMP2 OFF

17

2584

Value, in percent, that the heating control loop output must

 

 

 

go below for compressor 2 to turn OFF. Actual turn off is

 

 

 

subject to the CMP2 MlN ON time being expired.

 

 

 

 

WALL SWITCH

18

2583, 2584, 2590

YES indicates that the controller is to monitor the status of a

 

 

 

wall switch that is connected to Dl 2. NO indicates that the

 

 

 

controller will not monitor the status of a wall switch, even if

 

 

 

one is connected.

 

 

 

Valid input: YES or NO