Point Database
Description | Address | Application | Description |
|
|
|
|
RM STPT MlN | 11 | 2583, 2584 | Minimum temperature setpoint in degrees that the controller |
|
|
| can use from the setpoint dial. This overrides any |
|
|
| temperature setpoint from the setpoint dial that falls below |
|
|
| this minimum. |
|
|
| Valid entry range: 48° to 95°F (9° to 35°C) |
|
|
|
|
RM STPT MAX | 12 | 2583, 2584 | Maximum temperature setpoint in degrees that the controller |
|
|
| can use from the setpoint dial. This overrides any |
|
|
| temperature setpoint from the setpoint dial that raises above |
|
|
| this maximum. |
|
|
| Valid entry range: 48° to 95°F (9° to 35°C) |
|
|
|
|
RM STPT DIAL | {13} | 2583, 2584, 2590 | Temperature setpoint in degrees from the room temperature |
|
|
| sensor (not available on all temperature sensor models). |
|
|
| This setpoint will be used for control in day mode (heating or |
|
|
| cooling) when enabled by STPT DIAL (Point 14). |
|
|
| Valid entry range: 48° to 95°F (9° to 35°C) |
|
|
|
|
STPT DIAL | 14 | 2583, 2584 | YES indicates that there is a room setpoint dial on the room |
|
|
| temperature sensor and must be used as the temperature |
|
|
| setpoint for control in day/occupied mode. NO indicates that |
|
|
| the appropriate preset setpoint will be used as the |
|
|
| temperature setpoint for control in day/occupied heating or |
|
|
| cooling mode. |
|
|
| Valid input: YES or NO |
|
|
|
|
AUX TEMP | {15} | 2590 | Actual reading from a 10K Ω thermistor connected to the |
|
|
| controller's AI 5 input. When a thermistor is connected at |
|
|
| Al 5, DI 5 is not available. See DI 5. The physical input can |
|
|
| not be used for both analog and digital input at the same |
|
|
| time. |
MA TEMP | {15} | 2583, 2584 | Actual reading from a 10K Ω thermistor connected to the |
|
|
| controller's Al 5 input. When a thermistor is connected at |
|
|
| Al 5, DI 5 is not available. See DI 5. The physical input can |
|
|
| not be used for both analog and digital input at the same |
|
|
| time. |
|
|
|
|
CMP2 ON | 16 | 2583 | Value, in percent, that the active temperature control loop |
|
|
| output must exceed for compressor 2 to turn ON. Actual |
|
|
| turn on is subject to the CMP2 MlN OFF time being expired. |
HTG CMP2 ON | 16 | 2584 | Value, in percent, that the heating control loop output must |
|
|
| exceed for compressor 2 to turn ON. Actual turn on is |
|
|
| subject to the CMP2 MlN OFF time being expired. |
|
|
|
|
CMP2 OFF | 17 | 2583 | Value, in percent, that the active temperature control loop |
|
|
| output must go below for compressor 2 to turn OFF. Actual |
|
|
| turn off is subject to the CMP2 MlN ON time being expired. |
HTG CMP2 OFF | 17 | 2584 | Value, in percent, that the heating control loop output must |
|
|
| go below for compressor 2 to turn OFF. Actual turn off is |
|
|
| subject to the CMP2 MlN ON time being expired. |
|
|
|
|
WALL SWITCH | 18 | 2583, 2584, 2590 | YES indicates that the controller is to monitor the status of a |
|
|
| wall switch that is connected to Dl 2. NO indicates that the |
|
|
| controller will not monitor the status of a wall switch, even if |
|
|
| one is connected. |
|
|
| Valid input: YES or NO |