Siemens BACnet Heat Pump Controller - Multi-Stage Owner’s Manual

Description

Address

Application

Description

 

 

 

 

Dl OVRD SW

{19}

2583, 2584, 2590

Actual indication of the status of the override switch (not

 

 

 

physically available on all temperature sensor models) at the

 

 

 

room temperature sensor. ON indicates that the switch is

 

 

 

being pressed. OFF indicates that the switch is released.

 

 

 

Valid input: ON or OFF

OVRD TIME

20

2583, 2584

Amount of time in hours that the controller will operate in

 

 

 

day/occupied mode when the override switch is pressed

 

 

 

while the controller is in night/ unoccupied mode.

 

 

 

 

NGT OVRD

{21}

2583, 2584

Indicates the mode that the controller is operating in with

 

 

 

respect to the override switch. NIGHT indicates that the

 

 

 

switch has not been pressed and the override timer is not

 

 

 

active. DAY indicates that the switch has been pressed and

 

 

 

the override timer is active. The controller then uses a day

 

 

 

mode temperature setpoint. This point is only in effect when

 

 

 

DAY.NGT indicates night mode.

 

 

 

 

RMTMP OFFSET

22

All

Compensates for deviations between the value of ROOM

 

 

 

TEMP and the actual room temperature. This corrected

 

 

 

value is displayed in CTL TEMP.

 

 

 

RMTMP OFFSET + ROOM TEMP = CTL TEMP

FREE CLG

{23}

2583, 2584

Point commanded by the field panel PPCL to enable or

 

 

 

disable mixed air control (free cooling).

 

 

 

 

DI 2

{24}

2583, 2584, 2590

Actual status of a contact connected to the controller at Dl 2.

 

 

 

ON indicates that the contact is closed; OFF indicates that

 

 

 

the contact is open. If a wall switch is used, it is connected

 

 

 

to DI 2. See WALL SWITCH.

 

 

 

 

DI 5

{25}

2583, 2584, 2590

Actual status of a contact connected to the controller at

 

 

 

Al 5/Dl 5. ON indicates that the contact is closed; OFF

 

 

 

indicates that the contact is open. When a contact is

 

 

 

connected at Dl 5, Al 5 is not available. See Point number

 

 

 

15. The physical input can not be used for both analog and

 

 

 

digital input at the same time.

 

 

 

 

DI 6

{26}

2583, 2584, 2590

Actual status of a contact connected to the controller. ON

 

 

 

indicates that the contact is closed; OFF indicates that the

 

 

 

contact is open. Application 2583/2584: DI 6 can be used to

 

 

 

monitor an input that changes state when the heat pump is

 

 

 

in alarm. DI 6 can be unbundled to send alarm information

 

 

 

to the field panel for centralized alarm monitoring.

 

 

 

 

CMP2 MlN OFF

27

2583

Minimum time, in minutes, that compressor 2 will remain

 

 

 

OFF before turning ON.

HTG2 MlN OFF

27

2584

Minimum time, in minutes, that heating compressor 2 will

 

 

 

remain OFF before turning ON.

 

 

 

 

CMP2 MlN ON

28

2583

Minimum time, in minutes, that compressor 2 will remain ON

 

 

 

before turning OFF.

HTG2 MlN ON

28

2584

Minimum time, in minutes, that heating compressor 2 will

 

 

 

remain ON before turning OFF.

 

 

 

 

20

Siemens Building Technologies, Inc.

Page 28