Point Database
Description | Address | Application | Description |
|
|
|
|
DAY.NGT | {29} | 2583, 2584, 2590 | Indicates the mode in which the controller is operating. |
|
|
| Day temperature setpoints are used in day mode. |
|
|
| Night temperature setpoints are used in night mode. This |
|
|
| point is normally set by the field panel. |
|
|
|
|
CLG CMP1 ON | 30 | 2584 | Value, in percent, that the cooling temperature control loop |
|
|
| output must exceed for cooling compressor 1 to turn ON. |
|
|
| Actual turn on is subject to the CLG1 MlN OFF time being |
|
|
| expired. |
|
|
|
|
CLG CMP1 OFF | 31 | 2584 | Value, in percent, that the cooling temperature control loop |
|
|
| output must go below for cooling compressor 1 to turn OFF. |
|
|
| Actual turn off is subject to the CLG1 MlN ON time being |
|
|
| expired. |
|
|
|
|
CLG1 MlN OFF | 32 | 2584 | Minimum time, in minutes, that cooling compressor 1 will |
|
|
| remain OFF before turning ON. |
|
|
|
|
CLG1 MlN ON | 33 | 2584 | Minimum time, in minutes, that cooling compressor 1 will |
|
|
| remain ON before turning OFF. |
|
|
|
|
CLG CMP2 ON | 34 | 2584 | Value, in percent, that the cooling temperature control loop |
|
|
| output must exceed for cooling compressor 2 to turn ON. |
|
|
| Actual turn on is subject to the CLG 2 MIN OFF time being |
|
|
| expired. |
CMP3 ON | 34 | 2583 | Value, in percent, that the active temperature control loop |
|
|
| output must exceed for compressor 3 to turn ON. Actual |
|
|
| turn on is subject to the CMP3 MlN OFF time being expired. |
|
|
|
|
CLG CMP2 OFF | 35 | 2584 | Value, in percent, that the cooling temperature control loop |
|
|
| output must exceed for cooling compressor 2 to turn OFF. |
|
|
| Actual turn off is subject to the CLG2 MIN ON time being |
|
|
| expired. |
CMP3 OFF | 35 | 2583 | Value, in percent, that the active temperature control loop |
|
|
| output must go below for compressor 3 to turn OFF. Actual |
|
|
| turn off is subject to the CMP3 MlN ON time being expired. |
|
|
|
|
CLG2 MIN OFF | 36 | 2584 | Minimum time, in minutes, that cooling compressor 2 will |
|
|
| remain OFF before turning ON. |
CMP3 MlN OFF | 36 | 2583 | Minimum time, in minutes, that compressor 3 will remain |
|
|
| OFF before turning ON. |
|
|
|
|
CLG2 MlN ON | 37 | 2584 | Minimum time, in minutes, that cooling compressor 2 will |
|
|
| remain ON before turning OFF. |
CMP3 MlN ON | 37 | 2583 | Minimum time, in minutes, that compressor 3 will remain ON |
|
|
| before turning OFF. |
|
|
|
|
DAMPER TYPE | 38 | 2583, 2584 | FLOAT indicates that a floating control damper is used. |
|
|
| SPRING indicates that a spring return damper is used. |
|
|
| Valid input: FLOAT or SPRING. |
AO DIR.REV | 39 | 2583, 2584 | Configuration setup code for AO. Allows the AO to be direct |
|
|
| (normally closed) or reverse acting (normally open). |
|
|
|
|
AOV1 | {40} | 2583, 2584, 2590 | Analog output 1 controls a 0 to 10V signal. |
|
|
|
|