3
Point Database
Overview
This chapter presents a description of the Siemens BACnet Heat Pump
Description | Address | Application | Description |
|
|
|
|
CTLR ADDRESS | 01 | 2583, 2584, 2590 | ldentifies the controller on the FLN trunk. |
|
|
|
|
APPLICATION | 02 | 2583, 2584, 2590 | Identification number of the program running in the |
|
|
| controller. |
|
|
| Valid input: 2583, 2584, 2590 |
RETURN DELAY | 03 | 2583, 2584 | Amount of time the heat pump will remain off after a return |
|
|
| from power failure. |
|
|
|
|
ROOM TEMP | {04} | 2583, 2584, 2590 | Actual reading from the room temperature sensor. |
|
|
|
|
HEAT.COOL | {05} | 2583, 2584 | Current mode of operation for applications that can be either |
|
|
| a heating mode or a cooling mode. |
|
|
|
|
DAY CLG STPT | 06 | 2583, 2584 | Temperature setpoint in degrees that the controller |
|
|
| maintains during day periods in cooling mode if a room |
|
|
| temperature sensor setpoint dial is not present or is not |
|
|
| used. See STPT DIAL. |
|
|
| Valid entry range: 48° to 95°F (9°to 35°C) |
|
|
|
|
DAY HTG STPT | 07 | 2583, 2584 | Temperature setpoint in degrees that the controller |
|
|
| maintains during day periods in heating mode if a room |
|
|
| temperature sensor setpoint dial is not present or is not |
|
|
| used. See STPT DIAL. |
|
|
| Valid entry range: 48° to 95°F (9° to 35°C) |
|
|
|
|
NGT CLG STPT | 08 | 2583, 2584 | Temperature setpoint in degrees that the controller |
|
|
| maintains during night periods in cooling mode. |
|
|
| Valid entry range: 48° to 95°F (9° to 35°C) |
|
|
|
|
NGT HTG STPT | 09 | 2583, 2584 | Temperature setpoint in degrees that the controller |
|
|
| maintains during night periods in heating mode. |
|
|
| Valid entry range: 48° to 95°F (9° to 35°C) |
|
|
|
|
DMPR MlN POS | 10 | 2583, 2584 | Minimum position the damper will be commanded to during |
|
|
| day mode. |
|
|
|
|
Siemens Building Technologies, Inc. | 18 |