Point Database
Description | Address | Application | Description |
|
|
|
|
HTG LOOPOUT | {80} | 2583, 2584 | Heating temperature control loop output value in percent. |
|
|
|
|
ELEC HEAT ON | 81 | 2584 | Value, in percent, that the heating Ioopout must exceed for |
|
|
| the electric heat to turn ON. |
EHEAT 1 ON | 81 | 2583 | Value, in percent, that the heating loopout must exceed for |
|
|
| the first stage of electric heat to turn ON. |
|
|
|
|
CMP1 ON | 82 | 2583 | Value, in percent, that the active temperature control |
|
|
| loop output must exceed for compressor 1 to turn ON. |
|
|
| Actual turn on is subject to the CMP MlN OFF time being |
|
|
| expired. lt is also the value, in percent, which HTG |
|
|
| LOOPOUT must go below for the electric heat (ELEC HEAT |
|
|
| 1) to turn OFF when only one compressor is used. |
HTG CMP1 ON | 82 | 2584 | Value, in percent, that the heating temperature control loop |
|
|
| output must exceed for heating compressor 1 to turn ON. |
|
|
| Actual turn on is subject to the HTG1 MlN OFF time being |
|
|
| expired. |
|
|
|
|
CMP1 OFF | 83 | 2583 | Value, in percent, that the active temperature control loop |
|
|
| output must go below for compressor 1 to turn OFF. Actual |
|
|
| turn off is subject to the CMP1 MlN ON time being expired. |
HTG CMP1 OFF | 83 | 2584 | Value, in percent, that the heating temperature control loop |
|
|
| output must go below for heating compressor 1 to turn OFF. |
|
|
| Actual turn off is subject to the HTG1 MlN ON time being |
|
|
| expired. |
RVAL SWITCH | 84 | 2583 | Value, in percent, that the active temperature control loop |
|
|
| output must go above for the reversing valve to switch. |
|
|
| Actual switchover is subject to the status of HEAT.COOL, |
|
|
| RVAL SW TIME, and HTG LOOPOUT or CLG LOOPOUT. |
|
|
|
|
SWITCH LIMIT | 85 | 2583, 2584 | Active temperature control loop output must be less than |
|
|
| this value to switch between cooling mode and heating |
|
|
| mode. Actual switchover depends on SWITCH DBAND |
|
|
| being exceeded and is subject to SWITCH TIME being |
|
|
| expired. |
|
|
|
|
SWITCH TIME | 86 | 2583, 2584 | Time, in minutes, that must expire to switch between cooling |
|
|
| mode and heating mode. Actual switchover depends on the |
|
|
| active temperature control loop being below the value of |
|
|
| SWITCH LIMIT and exceeding the value of SWITCH |
|
|
| DBAND. |
|
|
|
|
CMP1 MlN OFF | 87 | 2583 | Minimum time, in minutes, that compressor 1 will remain |
|
|
| OFF before turning ON. |
HTG1 MlN OFF | 87 | 2584 | Minimum time, in minutes, that heating compressor 1 will |
|
|
| remain OFF before turning ON. |
|
|
|
|
CMP1 MlN ON | 88 | 2583 | Minimum time, in minutes, that compressor 1 will remain ON |
|
|
| before turning OFF. |
HTG1 MlN ON | 88 | 2584 | Minimum time, in minutes, that heating compressor 1 will |
|
|
| remain ON before turning OFF. |
|
|
|
|
RVAL SW TIME | 89 | 2583 | Length of time the compressor must be OFF before the |
|
|
| reversing valve can switch modes. |
|
|
|
|