DMPR POS

Point Database

Description

Address

Application

Description

 

 

 

 

DMPR POS

{49}

2583, 2584

Current position of the damper motor in percent of full travel.

 

 

 

This value is calculated based on motor run time.

MTR1 POS

{49}

2590

Current position of the damper motor in percent of full travel.

 

 

 

This value is calculated based on motor run time. See

 

 

 

MTR1 TIMING.

DO 8

{50}

2590

Digital output 8 controls a 24 Vac load with an ON or OFF

 

 

 

status.

FAN

{50}

2583, 2584

Digital output used to control the fan. ON indicates the DO is

 

 

 

energized; OFF indicates the DO is de-energized.

 

 

 

 

MTR TIMING

51

2583, 2584

Time required for the damper actuator to travel from full

 

 

 

closed to the full open position.

MTR1 TIMING

51

2590

Time required for the Motor 1 actuator to travel from full

 

 

 

closed to the full open position.

 

 

 

 

AI 3

{52}

2583, 2584, 2590

Spare analog input, switch selectable to be 0-10V or 4-

 

 

 

20mA (consult your Siemens Building Technologies

 

 

 

representative). Or, spare DI dry contact, see DI 3. The

 

 

 

physical input can not be used for both analog and digital

 

 

 

input at the same time.

 

 

 

 

AI 4

{53}

2583, 2584, 2590

Spare anolog input, 10K Ω thermistor. Or, spare DI dry

 

 

 

contact, see DI 4. The physical input can not be used for

 

 

 

both analog and digital input at the same time.

 

 

 

 

AOV 2

{54}

2583, 2584, 2590

Analog output 2 controls a 0 to 10V signal.

 

 

 

 

DI 3

{55}

2583, 2584, 2590

Actual status of a contact connected to the controller at

 

 

 

Dl 3. ON indicates that the contact is closed; OFF indicates

 

 

 

that the contact is open. When a contact is connected at Dl

 

 

 

3, Al 3 is not available. See AI 3. The physical input can not

 

 

 

be used for both analog and digital input at the same time.

 

 

 

 

DMPR ROT ANG

56

2583, 2584

Number of degrees the damper is free to travel.

DPR1 ROT ANG

56

2590

Number of degrees the damper is free to travel.

 

 

 

 

DI 4

{57}

2583, 2584, 2590

Actual status of a contact connected to the controller at

 

 

 

Dl 4. ON indicates that the contact is closed; OFF indicates

 

 

 

that the contact is open. When a contact is connected at Dl

 

 

 

4, Al 4 is not available. See AI 4. The physical input can not

 

 

 

be used for both analog and digital input at the same time.

 

 

 

 

MTR SETUP

58

2583, 2584, 2590

Configuration setup code for Motors 1 and 2. This enables

 

 

 

the motors individually and sets each motor to be either

 

 

 

direct or reverse acting.

 

 

 

NOTE: When a motor is enabled, its associated DOs are

 

 

 

enabled.

DO DIR.REV

59

2583, 2584, 2590

Configuration setup code for DOs. Allows the DOs to be

 

 

 

direct or reverse acting (enabled equals energized or

 

 

 

disabled equals de-energized).

 

 

 

 