Point Database
Description | Address | Application | Description |
|
|
|
|
DMPR POS | {49} | 2583, 2584 | Current position of the damper motor in percent of full travel. |
|
|
| This value is calculated based on motor run time. |
MTR1 POS | {49} | 2590 | Current position of the damper motor in percent of full travel. |
|
|
| This value is calculated based on motor run time. See |
|
|
| MTR1 TIMING. |
DO 8 | {50} | 2590 | Digital output 8 controls a 24 Vac load with an ON or OFF |
|
|
| status. |
FAN | {50} | 2583, 2584 | Digital output used to control the fan. ON indicates the DO is |
|
|
| energized; OFF indicates the DO is |
|
|
|
|
MTR TIMING | 51 | 2583, 2584 | Time required for the damper actuator to travel from full |
|
|
| closed to the full open position. |
MTR1 TIMING | 51 | 2590 | Time required for the Motor 1 actuator to travel from full |
|
|
| closed to the full open position. |
|
|
|
|
AI 3 | {52} | 2583, 2584, 2590 | Spare analog input, switch selectable to be |
|
|
| 20mA (consult your Siemens Building Technologies |
|
|
| representative). Or, spare DI dry contact, see DI 3. The |
|
|
| physical input can not be used for both analog and digital |
|
|
| input at the same time. |
|
|
|
|
AI 4 | {53} | 2583, 2584, 2590 | Spare anolog input, 10K Ω thermistor. Or, spare DI dry |
|
|
| contact, see DI 4. The physical input can not be used for |
|
|
| both analog and digital input at the same time. |
|
|
|
|
AOV 2 | {54} | 2583, 2584, 2590 | Analog output 2 controls a 0 to 10V signal. |
|
|
|
|
DI 3 | {55} | 2583, 2584, 2590 | Actual status of a contact connected to the controller at |
|
|
| Dl 3. ON indicates that the contact is closed; OFF indicates |
|
|
| that the contact is open. When a contact is connected at Dl |
|
|
| 3, Al 3 is not available. See AI 3. The physical input can not |
|
|
| be used for both analog and digital input at the same time. |
|
|
|
|
DMPR ROT ANG | 56 | 2583, 2584 | Number of degrees the damper is free to travel. |
DPR1 ROT ANG | 56 | 2590 | Number of degrees the damper is free to travel. |
|
|
|
|
DI 4 | {57} | 2583, 2584, 2590 | Actual status of a contact connected to the controller at |
|
|
| Dl 4. ON indicates that the contact is closed; OFF indicates |
|
|
| that the contact is open. When a contact is connected at Dl |
|
|
| 4, Al 4 is not available. See AI 4. The physical input can not |
|
|
| be used for both analog and digital input at the same time. |
|
|
|
|
MTR SETUP | 58 | 2583, 2584, 2590 | Configuration setup code for Motors 1 and 2. This enables |
|
|
| the motors individually and sets each motor to be either |
|
|
| direct or reverse acting. |
|
|
| NOTE: When a motor is enabled, its associated DOs are |
|
|
| enabled. |
DO DIR.REV | 59 | 2583, 2584, 2590 | Configuration setup code for DOs. Allows the DOs to be |
|
|
| direct or reverse acting (enabled equals energized or |
|
|
| disabled equals |
|
|
|
|
Siemens Building Technologies, Inc. | 23 |