Siemens BACnet Heat Pump Controller -
Description | Address | Application | Description |
|
|
|
|
CYCLE FAN | 60 | 2583, 2584 | YES indicates that the fan should cycle ON and OFF with |
|
|
| the compressor during day mode. NO indicates that the fan |
|
|
| should remain ON constantly in day mode. |
|
|
| Valid input: YES or NO |
|
|
| NOTE: In either case, the fan will cycle during night mode. |
|
|
|
|
FREE CLG ON | 61 | 2583, 2584 | Value, in percent, that the cooling loopout must exceed for |
|
|
| free cooling to turn ON. |
|
|
|
|
FREE CLG OFF | 62 | 2583, 2584 | Value, in percent, that the cooling loopout must exceed for |
|
|
| free cooling to turn OFF. |
CLG P GAIN | 63 | 2583, 2584 | Proportional gain value for the cooling temperature control |
|
|
| loop. |
|
|
|
|
CLG I GAIN | 64 | 2583, 2584 | Integral gain value for the cooling temperature control loop. |
|
|
|
|
STPT SPAN | 65 | 2583, 2584 | Used to configure the allowable temperature range when |
|
|
| using the optional Relative Setpoint Adjustment feature. |
|
|
|
|
STAT TYPE | 66 | 2583, 2584 | Default = NORMAL. Can be set to OFFSET for optional |
|
|
| Relative Setpoint Adjustment feature when room sensor part |
|
|
| number |
|
|
| Valid input: NORMAL or OFFSET |
|
|
|
|
HTG P GAIN | 67 | 2583, 2584 | Proportional gain value for the heating temperature control |
|
|
| loop. |
|
|
|
|
HTG I GAIN | 68 | 2583, 2584 | Integral gain value for the heating temperature control loop. |
|
|
|
|
HP DO OVRD | 69 | 2583, 2584 | For the commanding of critical digital outputs. CAUTION: |
|
|
| IMPROPER USE CAN CAUSE PERMANENT EQUIPMENT |
|
|
| DAMAGE. |
|
|
|
|
STPT OFFSET | {70} | 2583, 2584 | For use with optional Relative Setpoint Adjustment feature. |
|
|
|
|
MA P GAIN | {71} | 2583, 2584 | Proportional gain value for the mixed air control loop. |
|
|
|
|
MA I GAIN | {72} | 2583, 2584 | Integral gain value for the mixed air control loop. |
|
|
|
|
MA D GAIN | {73} | 2583, 2584 | Derivative gain value for the mixed air control loop. |
|
|
|
|
MA BIAS | {74} | 2583, 2584 | Biasing of the mixed air control loop. |
|
|
|
|
CMP TOTL | 75 | 2583 | Number of compressors used by the application. |
|
|
| Valid values: 0, 1, 2, 3 |
HTG CMP TOTL | 75 | 2584 | Number of heating compressors used by the application. |
|
|
| Valid values: 0, 1, 2 |
|
|
|
|
EHTG STG CNT | 76 | 2583, 2584 | Number of electric heating stages used by the application. |
|
|
| Valid values: 0, 1, 2, 3 |
CLG CMP TOTL | 77 | 2584 | Number of cooling compressors used by the application. |
|
|
| Valid values: 0, 1, 2 |
CTL TEMP | {78} | 2583, 2584, 2590 | Temperature used as input for the temperature |
|
|
| control loops. This value will be the same as the value in |
|
|
| ROOM TEMP + RMTMP OFFSET unless it is overridden. |
|
|
|
|
CLG LOOPOUT | {79} | 2583, 2584 | Cooling temperature control loop output value in percent. |
|
|
|
|
24 | Siemens Building Technologies, Inc. |