Siemens 125-699 owner manual Valid input NORMAL or OFFSET

Models: 125-699

1 43
Download 43 pages 27.96 Kb
Page 32
Image 32
Valid input: NORMAL or OFFSET

Siemens BACnet Heat Pump Controller - Multi-Stage Owner’s Manual

Description

Address

Application

Description

 

 

 

 

CYCLE FAN

60

2583, 2584

YES indicates that the fan should cycle ON and OFF with

 

 

 

the compressor during day mode. NO indicates that the fan

 

 

 

should remain ON constantly in day mode.

 

 

 

Valid input: YES or NO

 

 

 

NOTE: In either case, the fan will cycle during night mode.

 

 

 

 

FREE CLG ON

61

2583, 2584

Value, in percent, that the cooling loopout must exceed for

 

 

 

free cooling to turn ON.

 

 

 

 

FREE CLG OFF

62

2583, 2584

Value, in percent, that the cooling loopout must exceed for

 

 

 

free cooling to turn OFF.

CLG P GAIN

63

2583, 2584

Proportional gain value for the cooling temperature control

 

 

 

loop.

 

 

 

 

CLG I GAIN

64

2583, 2584

Integral gain value for the cooling temperature control loop.

 

 

 

 

STPT SPAN

65

2583, 2584

Used to configure the allowable temperature range when

 

 

 

using the optional Relative Setpoint Adjustment feature.

 

 

 

 

STAT TYPE

66

2583, 2584

Default = NORMAL. Can be set to OFFSET for optional

 

 

 

Relative Setpoint Adjustment feature when room sensor part

 

 

 

number SB1-0916 or SB1-1072 is used.

 

 

 

Valid input: NORMAL or OFFSET

 

 

 

 

HTG P GAIN

67

2583, 2584

Proportional gain value for the heating temperature control

 

 

 

loop.

 

 

 

 

HTG I GAIN

68

2583, 2584

Integral gain value for the heating temperature control loop.

 

 

 

 

HP DO OVRD

69

2583, 2584

For the commanding of critical digital outputs. CAUTION:

 

 

 

IMPROPER USE CAN CAUSE PERMANENT EQUIPMENT

 

 

 

DAMAGE.

 

 

 

 

STPT OFFSET

{70}

2583, 2584

For use with optional Relative Setpoint Adjustment feature.

 

 

 

 

MA P GAIN

{71}

2583, 2584

Proportional gain value for the mixed air control loop.

 

 

 

 

MA I GAIN

{72}

2583, 2584

Integral gain value for the mixed air control loop.

 

 

 

 

MA D GAIN

{73}

2583, 2584

Derivative gain value for the mixed air control loop.

 

 

 

 

MA BIAS

{74}

2583, 2584

Biasing of the mixed air control loop.

 

 

 

 

CMP TOTL

75

2583

Number of compressors used by the application.

 

 

 

Valid values: 0, 1, 2, 3

HTG CMP TOTL

75

2584

Number of heating compressors used by the application.

 

 

 

Valid values: 0, 1, 2

 

 

 

 

EHTG STG CNT

76

2583, 2584

Number of electric heating stages used by the application.

 

 

 

Valid values: 0, 1, 2, 3

CLG CMP TOTL

77

2584

Number of cooling compressors used by the application.

 

 

 

Valid values: 0, 1, 2

CTL TEMP

{78}

2583, 2584, 2590

Temperature used as input for the temperature

 

 

 

control loops. This value will be the same as the value in

 

 

 

ROOM TEMP + RMTMP OFFSET unless it is overridden.

 

 

 

 

CLG LOOPOUT

{79}

2583, 2584

Cooling temperature control loop output value in percent.

 

 

 

 

24

Siemens Building Technologies, Inc.

Page 32
Image 32
Siemens 125-699 owner manual Valid input NORMAL or OFFSET