Issue 03/01 9 Electro-Magnetic Compatibility (EMC)
MICROMASTER 411 & COMBIMASTER 411 Operating Instructions
6SE6400-5CA00-0BP0
111
Hinsichtlich des EMV-Verhaltens gibt es drei allgemeine Klassen, wie nachstehend
spezifiziert:
Environment: General Industrial
Compliance with the EMC Product Standard for Power Drive Systems EN 61800-3
for use in Second Environment (Industrial) and Restricted Distribution.
Table 9-1 Environment - General Industrial
EMC Phenomenon Standard Level
Emissions:
Radiated Emissions EN 55011 Level A1
Conducted Emissions EN 61800-3 European Amendment EN61800-3-A13
Immunity:
Electrostatic Discharge EN 61000-4-2 8 kV air discharge
Burst Interference EN 61000-4-4 2 kV power cables, 1 kV control
Radio Frequency Electromagnetic Field IEC 1000-4-3 26-1000 MHz, 10 V/m
Environment: Filtered Industrial
This level of performance will allow the manufacturer/assembler to self-certify their
apparatus for compliance with the EMC directive for the industrial environment as
regards the EMC performance characteristics of the power drive system.
Performance limits are as specified in the Generic Industrial Emissions and
Immunity standards EN 50081-2 and EN 50082-2.
Table 9-2 Environment - Filtered Industrial
EMC Phenomenon Standard Level
Emissions:
Radiated Emissions EN 55011 Level A1
Conducted Emissions EN 55011 Level A1
Immunity:
Supply Voltage Distortion IEC 1000-2-4
(1993)
Voltage Fluctuations, Dips, Unbalance,
Frequency Variations
IEC 1000-2-1
Magnetic Fields EN 61000-4-8 50 Hz, 30 A/m
Electrostatic Discharge EN 61000-4-2 8 kV air discharge
Burst Interference EN 61000-4-4 2 kV power cables, 2 kV control
Radio Frequency Electromagnetic
Field, amplitude modulated
ENV 50 140 80-1000 M Hz, 10 V/m, 80% AM, power
and signal lines
Radio-frequency Electromagnetic Field,
pulse modulated
ENV 50 204 900 MHz, 10 V/ m 50% duty cycle, 200 Hz
repetition rate