5 System Parameters Issue 03/01
MICROMASTER 411 & COMBIMASTER 411 Operating Instructions
78
6SE6400-5CA00-0BP0
ParNr ParText Default Acc WS QC
P2255 PID setpoint gain factor 100.00 3 CUT N
P2256 PID trim gain factor 100.00 3 CUT N
P2257 Ramp-up time for PID setpoint 1.00 2 CUT N
P2258 Ramp-down time for PID setpoint 1.00 2 CUT N
r2260 CO: PID setpoint after PID-RFG - 2 - -
P2261 PID setpoint filter timeconstant 0.00 3 CUT N
r2262 CO: Filtered PID setp. after RFG - 3 - -
P2264[1] CI: PID feedback 755:0 2 CUT N
P2265 PID feedback filter timeconstant 0.00 2 CUT N
r2266 CO: PID filtered feedback - 2 - -
P2267 Max. value for PID feedback 100.00 3 CUT N
P2268 Min. value for PID feedback 0.00 3 CUT N
P2269 Gain applied to PID feedback 100.00 3 CUT N
P2270 PID feedback function selector 0 3 CUT N
P2271 PID transducer type 0 2 CUT N
r2272 CO: PID scaled feedback - 2 - -
r2273 CO: PID error - 2 - -
P2280 PID proportional gain 3.000 2 CUT N
P2285 PID integral time 0.000 2 CUT N
P2291 PID output upper limit 100.00 2 CUT N
P2292 PID output lower limit 0.00 2 CUT N
P2293 Ramp-up /-down time of PID limit 1.00 3 CUT N
r2294 CO: Act. PID output - 2 - -
P2390 Energy saving setpoint 0 3 CUT N
P2391 Energy saving timer 0 3 CT N
P2392 Energy saving restart setpoint 0 3 CT N
P2393 EnerSav changeover threshold 90.0 3 CUT N
P2394 Energy saving low characteristic 0.00 3 CUT N
P2395 Energy saving up characteristic 0.00 3 CUT N
P2396[1] CI: Torque 86:0 2 CUT N
P2397 Torque filtered timeconstant 0.00 2 CUT N
r2398 CO: Filtered torque 2 - -
r2399 CO/BO: Energy Saving status word 3 - -