Issue 03/01 5 System Parameters
MICROMASTER 411 & COMBIMASTER 411 Operating Instructions
6SE6400-5CA00-0BP0
73
ParNr ParText Default Acc WS QC
P1142[1] BI: RFG enable setpoint 1:0 3 CT N
P1230[1] BI: Enable DC braking 0:0 3 CUT N
P2103[1] BI: 1. Faults acknowledgement 722:2 3 CT N
P2104[1] BI: 2. Faults acknowledgement 0:0 3 CT N
P2106[1] BI: External fault 1:0 3 CT N
P2220[1] BI: Fixed PID setp. select Bit 0 0:0 3 CT N
P2221[1] BI: Fixed PID setp. select Bit 1 0:0 3 CT N
P2222[1] BI: Fixed PID setp. select Bit 2 0:0 3 CT N
P2235[1] BI: Enable PID-MOP (UP-cmd) 19:13 3 CT N
P2236[1] BI: Enable PID-MOP (DOWN-cmd) 19:14 3 CT N
Analogue I/O (P0004 = 8)
r0750 Number of ADCs - 3 - -
r0752[2] Act. input of ADC [V] - 2 - -
P0753[1] Smooth time ADC 3 3 CUT N
r0754[2] Act. ADC value after scaling [%] - 2 - -
r0755[2] CO: Act. ADC after scal. [4000h] - 2 - -
P0756[1] Type of ADC 0 2 CT N
P0757[1] Value x1 of ADC scaling [V] 0 2 CUT N
P0758[1] Value y1 of ADC scaling 0.0 2 CUT N
P0759[1] Value x2 of ADC scaling [V] 10 2 CUT N
P0760[1] Value y2 of ADC scaling 100.0 2 CUT N
P0761[1] Width of ADC deadband [V] 0 2 CUT N
P0762[1] Delay for loss of signal action 10 3 CUT N
Setpoint Channel and Ramp Generator (P0004 = 10)
ParNr ParText Default Acc WS QC
P1000[1] Selection of frequency setpoint 27 1 CT Q
P1001[1] Fixed frequency 1 0.00 2 CUT N
P1002[1] Fixed frequency 2 5.00 2 CUT N
P1003[1] Fixed frequency 3 10.00 2 CUT N
P1004[1] Fixed frequency 4 15.00 2 CUT N
P1005[1] Fixed frequency 5 20.00 2 CUT N
P1006[1] Fixed frequency 6 25.00 2 CUT N
P1007[1] Fixed frequency 7 30.00 2 CUT N
P1016 Fixed frequency mode – Bit 0 1 3 CT N
P1017 Fixed frequency mode – Bit 1 1 3 CT N
P1018 Fixed frequency mode – Bit 2 1 3 CT N
r1024 CO: Act. fixed frequency - 3 - -
P1031[1] Setpoint memory of the MOP 0 2 CUT N
P1032 Inhibit reverse direction of MOP 1 2 CT N
P1040[1] Setpoint of the MOP 5.00 2 CUT N
r1050 CO: Act. Output freq. of the MOP - 3 - -
P1058[1] JOG frequency right 5.00 2 CUT N
P1059[1] JOG frequency left 5.00 2 CUT N