3 Commissioning Issue 03/01
MICROMASTER 411 & COMBIMASTER 411 Operating Instructions
52
6SE6400-5CA00-0BP0
Changing parameters with the BOP The procedure for changing the value of parameter P0004 is described below.
Modifying the value of an indexed parameter is illustrated using the example of
P0719. Follow exactly the same procedure to alter other parameters that you wish
to set via the BOP.
Changing P0004 – parameter filter function
Step Result on display
1
Press to access parameters
2 Press until P0004 is displayed
3 Press to access the parameter value level
4 Press or to the required value
5 Press to confirm and store the value
6 Only the command paramet ers are visible to the user.
Changing P0719 an indexed parameter
Selection of command/setpoint source
Step
Result on display
1 Press to access parameters
2 Press until P0719 is displayed
3 Press to access the parameter value level
4 Press to display current set value
5 Press or to the required value
6 Press to confirm and store the value
7 Press until r0000 is displayed
8 Press to return the display to the standard drive display (as
defined by the customer)
Figure 3-6 Changing parameters via the BOP
NOTE
In some cases - when changing parameter values - the display on the BOP shows
. This means the inverter is busy with tasks of higher priority.