Issue 03/01 3 Commissioning
MICROMASTER 411 & COMBIMASTER 411 Operating Instructions
6SE6400-5CA00-0BP0
49
To change parameters it is necessary to use a Basic Operator Panel (BOP),
Advanced Operator Panel (AOP) or an external serial interface with DriveMonitor
or STARTER. The inverter is therefore delivered with the following default settings:
Setpoint control from the Analog input in addition to Control Potentiometer.
Supply frequency set for 0 to 50 Hz.
Digital inputs:
DIN 1 ON/OFF1.
DIN 2 Reverse.
DIN 3 Fault Acknowledge
Jumpers for Ramp and Control circuits set to open (default settings). Refer to
sections 3.3.1 and 3.3.2.
Relay – Fault conditions.
Prerequisites
Mechanical and electrical Installation is completed.
NOTE
We recommend the commissioning according this scheme.
Setting the motor frequency
Jumper 60Hz: OFF = 50 Hz / ON = 60 Hz
Quick Commissioning P0010 = 1
See Section 3.3.4.3
Further Commissioning via P0004 and P0003
An overview of the parameter structure is given in
Section 5.3
For a detailed description of parameters, see the
Parameter List.
Power ON