Issue 03/01 2 Installation
MICROMASTER 411 & COMBIMASTER 411 Operating Instructions
6SE6400-5CA00-0BP0
37
1. Feed the control cables into the inverter via one of the gland holes at the I/O
module end of the terminal housing.
2. Run the control cable underneath the I/O board toward the control terminals.
3. Connect the control wires in accordance with the terminal information given in
Figure 2-11.
4. Use screened cable for all control wiring.
8 9
1 2 3 4 5 6 7
Terminal Inputs Parameter Default operation
1 DIN 1 P0701 = ‘1’ ON/OFF1
2 DIN 2 P0702 = ‘12’ Reverse
3 DIN 3 P0703 = ‘9’ Fault Acknowledge
6/7 AIN (-/+) P0756 = 0 0 – 10 V Analogue Input
Option: DIN 4 P0704 ≠ 0
8/9 Output Relay P0731 = ’52.3’ Fault identification
Figure 2-11 Control Terminals
NOTE
If a PTC resistor is fitted, this
should be connected between 4
(+24 V) and 3 (DIN 3).