Simplicity 514067-UAD-A-0509 manual ALARM3

Models: 514067-UAD-A-0509

1 18
Download 18 pages 25.18 Kb
Page 11
Image 11

514067-UAD-A-0509

TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)

 

BACnet

BACnet

 

 

 

 

 

Read/

Object

Object

 

 

 

 

 

Write

Type

Inst

Descriptor

Default

Min

Max

Point Description

R

(2) AV

38

ALARM_3

System Alarm #3

R

(2) AV

39

ALARM_4

System Alarm #4

R

(2) AV

40

ALARM_5

System Alarm #5

R

(2) AV

41

E_C1_ACM_HRS

Elite Compressor #1 Accumulated Run Time

 

 

 

 

 

 

 

(in hours)

R

(2) AV

42

E_C2_ACM_HRS

Elite Compressor #2 Accumulated Run Time

 

 

 

 

 

 

 

(in hours)

R

(2) AV

43

E_C3_ACM_HRS

Elite Compressor #3 Accumulated Run Time

 

 

 

 

 

 

 

(in hours)

R

(2) AV

44

E_C4_ACM_HRS

Elite Compressor #4 Accumulated Run Time

 

 

 

 

 

 

 

(in hours)

R

(2) AV

45

I_C1_ACM_HRS

Intelli-Comfort Compressor #1 Accumulated

 

 

 

 

 

 

 

Run Time (in hours)

R

(2) AV

46

I_C2_ACM_HRS

Intelli-Comfort Compressor #2 Accumulated

 

 

 

 

 

 

 

Run Time (in hours)

R

(2) AV

47

HGR_VLV_OUT

Hot Gas Reheat Valve Output Status

 

 

 

 

 

 

 

(0-100%)

R

(2) AV

48

NUMBER_HEAT

Number of Heat Stages Available

R

(2) AV

49

OP_HEAT_STPT

68

45

99

Operating Heating Setpoint

R/W

(2) AV

50

OCC_HEAT_SP

68

45

99

Occupied Heating Setpoint

R/W

(2) AV

51

UNOC_HEAT_SP

60

45

99

Un-Occupied Heating Setpoint

R/W

(2) AV

52

SAT_HEAT_SP

135

100

180

Supply Air Temperature Limit for Heating

 

 

 

 

 

 

 

Setpoint (degrees F)

R/W

(2) AV

53

SAT_ALM_HEAT

0

0

120

Supply Air Temperature Alarm Setpoint for

 

 

 

 

 

 

 

Heating

R/W

(2) AV

54

OAT_HEAT_L_O

75

0

100

Outdoor Air Temperature HeatingLockout

 

 

 

 

 

 

 

Temperature

R

(2) AV

55

HW_VLV_OUT

Hot Water Valve Output Status (0-100%)

R

(2) AV

56

CV_VAV_SELEC

CV/VAV Selected (0= Valid CV, 1=Valid VAV,

 

 

 

 

 

 

 

2= Invalid Value)

R/W

(2) AV

57

BLDG_SP_STPT

0.1

-0.25

0.25

Building Static Pressure Setpoint

R/W

(2) AV

58

DUCT_SP_STPT

1.5

0

5

Duct Static Pressure Setpoint

R/W

(2) AV

59

DUCT_SD_STPT

4.5

0

5

Duct Static Pressure Shutdown Setpoint

R/W

(2) AV

60

VAV_OHEAT_SP

68

40

85

VAV Occupied Heating Setpoint (degrees F)

R/W

(2) AV

61

MWU_RAT_STPT

70

50

85

Morning Warm-Up and VAV Heating: Return

 

 

 

 

 

 

 

Air Temperature Setpoint (degrees F)

R/W

(2) AV

62

HYD_S1_SA_SP

120

80

180

Hydronic Heating Stage #1 Supply Air

 

 

 

 

 

 

 

Setpoint (degrees F)

R/W

(2) AV

63

HYD_S2_SA_SP

150

80

180

Hydronic Heating Stage #2 Supply Air

 

 

 

 

 

 

 

Setpoint (degrees F)

R/W

(2) AV

64

VAV_CL_HI_SP

60

40

70

VAV Cooling Supply Air Temperature: Upper

 

 

 

 

 

 

 

Setpoint (degrees F)

R/W

(2) AV

65

VAV_CL_LO_SP

55

40

70

VAV Cooling Supply Air Temperature: Lower

 

 

 

 

 

 

 

Setpoint (degrees F)

R/W

(2) AV

66

VAV_SAT_RSET

72

40

85

VAV Cooling Supply Air Temperature: Reset

 

 

 

 

 

 

 

Setpoint (Space Temperature) (degrees F)

R

(2) AV

67

REVISION

0

0

xx

Device Revision

Johnson Controls Unitary Products

11

Page 11