TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED) |
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
| BACnet | BACnet |
|
|
|
|
|
|
|
| Read/ | Object | Object |
|
|
|
|
|
|
|
| Write | Type | Inst | Descriptor | Default | Min | Max | Point Description |
| |
| R | (5) BV | 66 | E_FREEZE_ST | – | – | – | Hot H2O Freeze Thermostat Switch #1 | ||
|
|
|
|
|
|
|
| Input Status (1=closed, 0=open/fault) |
| |
| R | (2) AV | 55 | HW_VLV_OUT | – | – | – | Hot Water Valve Output Status |
| |
| R | (5) BV | 2 | HYDRONC_HEAT | – | – | – | Hydronic Heat Enabled |
| |
| R | (5) BV | 3 | HH_REVER_VLV | – | – | – | Hydronic Heat Reverse Actuated Valve | ||
|
|
|
|
|
|
|
| Installed |
| |
| R/W | (2) AV | 62 | HYD_S1_SA_SP | 120 | 80 | 180 | Hydronic Heating Stage #1 Supply Air | ||
|
|
|
|
|
|
|
| Setpoint (degrees F) |
| |
| R/W | (2) AV | 63 | HYD_S2_SA_SP | 150 | 80 | 180 | Hydronic Heating Stage #2 Supply Air | ||
|
|
|
|
|
|
|
| Setpoint (degrees F) |
| |
| R/W | (2) AV | 80 | IO_DVNT_STPT | 700 | 0 | 2000 | Indoor/Outdoor Demand Ventilation | ||
|
|
|
|
|
|
|
| Setpoint |
| |
| R | (2) AV | 45 | I_C1_ACM_HRS | – | – | – | |||
|
|
|
|
|
|
|
| Run Time (in hours) |
| |
| R | (5) BV | 73 | I_COMP1_STAT | – | – | – | |||
|
|
|
|
|
|
|
| (0=output is OFF, 1=output is ON) |
| |
| R | (2) AV | 46 | I_C2_ACM_HRS | – | – | – | |||
|
|
|
|
|
|
|
| Run Time (in hours) |
| |
| R | (5) BV | 76 | I_COMP2_STAT | – | – | – | |||
|
|
|
|
|
|
|
| (0=output is OFF, 1=output is ON) |
| |
| R | (5) BV | 79 | I_CFAN_STAT | – | – | – | |||
|
|
|
|
|
|
|
| Status (0=output is OFF, 1=output is ON) |
| |
| R | (5) BV | 72 | I_FAN_OVER | – | – | – | |||
|
|
|
|
|
|
|
| Status (0=open,1=closed) |
| |
| R | (5) BV | 82 | I_FREEZE_1 | – | – | – | |||
|
|
|
|
|
|
|
| Input Status (0=open,1=closed) |
| |
| R | (5) BV | 83 | I_FREEZE_2 | – | – | – | |||
|
|
|
|
|
|
|
| Input Status (0=open,1=closed) |
| |
| R | (5) BV | 80 | I_GAS_VLVE1 | – | – | – |
| ||
| R | (5) BV | 75 | I_HPS1 | – | – | – | |||
|
|
|
|
|
|
|
| Compressor #1 Input Status (1=closed, | ||
|
|
|
|
|
|
|
| 0=open/fault) |
| |
| R | (5) BV | 78 | I_HPS2 | – | – | – | |||
|
|
|
|
|
|
|
| Compressor #2 Input Status (1=closed, | ||
|
|
|
|
|
|
|
| 0=open/fault) |
| |
| R | (5) BV | 71 | I_IFAN_STAT | – | – | – | |||
|
|
|
|
|
|
|
| (0=output is OFF, 1=output is ON) |
| |
| R | (5) BV | 81 | I_LIMIT_1 | – | – | – |
| ||
| R | (5) BV | 74 | I_LPS1 | – | – | – | |||
|
|
|
|
|
|
|
| Compressor #1 Input Status (1=closed, | ||
|
|
|
|
|
|
|
| 0=open/fault) |
| |
| R | (5) BV | 77 | I_LPS2 | – | – | – | |||
|
|
|
|
|
|
|
| Compressor #2 Input Status (1=closed, | ||
|
|
|
|
|
|
|
| 0=open/fault) |
| |
| R | (5) BV | 28 | – | – | – |
| |||
| R/W | (5) BV | 13 | LOADSHED | – | – | – | Loadshed (0=clear loadshed, 1=set load- | ||
|
|
|
|
|
|
|
| shed operation) |
| |
| R | (5) BV | 19 | LOW_AMB_OVRD | – | – | – | Low Ambient Temperature (0=comps not | ||
|
|
|
|
|
|
|
| overridden by LAT, 1=comps overridden) |
|