TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor Default Min Max Point Description
R/W (2) AV 20 ECO_1ST_STPT 55 40 65 Economizer First Stage Setpoint
R (5) BV 7 ECONO_INST Economizer Installed
R (5) BV 36 ECO_L_TO_SAT Economizer Loading to Control Supply Air
Temperature Enabled
R/W (2) AV 19 ECON_MIN_POS 20 0 100 Economizer Minimum Position
R (5) BV 31 ECONO_STATUS Economizer Output Status (0=not Free
Cooling, 1= Free Cooling)
R/W (2) AV 22 ECON_OAEN_SP 27 10 50 Economizer Outside Air Enthalpy Setpoint
R/W (2) AV 23 ECON_OAT_ENA 55 40 80 Economizer Outside Air Temperature
Enable Setpoint
R/W (2) AV 84 ECON_RAEN_SP 27 10 50 Economizer Return Air Enthalpy Setpoint
R/W (2) AV 21 ECO_2ND_STPT 50 40 65 Economizer Second Stage Setpoint
R (2) AV 41 E_C1_ACM_HRS Elite Compressor #1 Accumulated Run
Time (in hours)
R (5) BV 42 E_COMP1_STAT Elite Compressor #1 Output Status (0=out-
put is OFF, 1=output is ON)
R (5) BV 45 E_C1_OVRLOAD Elite Compressor #1 Overload Switch Input
Status (1=closed, 0=open/fault)
R (2) AV 42 E_C2_ACM_HRS Elite Compressor #2 Accumulated Run
Time (in hours)
R (5) BV 46 E_COMP2_STAT Elite Compressor #2 Output Status (0=out-
put is OFF, 1=output is ON)
R (5) BV 49 E_C2_OVRLOAD Elite Compressor #2 Overload Switch Input
Status (1=closed, 0=open/fault)
R (2) AV 43 E_C3_ACM_HRS Elite Compressor #3 Accumulated Run
Time (in hours)
R (5) BV 51 E_COMP3_STAT Elite Compressor #3 Output Status (0=out-
put is OFF, 1=output is ON)
R (5) BV 54 E_C3_OVRLOAD Elite Compressor #3 Overload Switch Input
Status (1=closed, 0=open/fault)
R (2) AV 44 E_C4_ACM_HRS Elite Compressor #4 Accumulated Run
Time (in hours)
R (5) BV 55 E_COMP4_STAT Elite Compressor #4 Output Status (0=out-
put is OFF, 1=output is ON)
R (5) BV 58 E_C4_OVRLOAD Elite Compressor #4 Overload Switch Input
Status (1=closed, 0=open/fault)
R (5) BV 50 E_CFAN1_STAT Elite Condenser Fan #1 Output Status
(0=output is OFF, 1=output is ON)
R (5) BV 59 E_CFAN2_STAT Elite Condenser Fan #2 Output Status Input
Status (0=output is OFF, 1=output is ON)
R (5) BV 41 E_FAN_ OVER Elite Fan Overload Switch Input Status
(1=closed, 0=open/fault)
R (5) BV 60 E_GAS_VLVE1 Elite Gas Valve #1 Input Status (1=ener-
gized, 0=not energized)
R (5) BV 62 E_GAS_VLVE2 Elite Gas Valve #2 Input Status (1=ener-
gized, 0=not energized)
R (5) BV 64 E_GAS_VLVE3 Elite Gas Valve #3 Input Status (1=ener-
gized, 0=not energized)