514067-UAD-A-0509

TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)

 

BACnet

BACnet

 

 

 

 

 

Read/

Object

Object

 

 

 

 

 

Write

Type

Inst

Descriptor

Default

Min

Max

Point Description

R

(5) BV

47

E_LPS2

Elite Low Pressure Switch for Compressor

 

 

 

 

 

 

 

#2 Input Status (1=closed, 0=open/fault)

R

(5) BV

48

E_HPS2

Elite High Pressure Switch for Compressor

 

 

 

 

 

 

 

#2 Input Status (1=closed, 0=open/fault)

R

(5) BV

49

E_C2_OVRLOAD

Elite Compressor #2 Overload Switch Input

 

 

 

 

 

 

 

Status (1=closed, 0=open/fault)

R

(5) BV

50

E_CFAN1_STAT

Elite Condenser Fan #1 Output Status

 

 

 

 

 

 

 

(0=output is OFF, 1=output is ON)

R

(5) BV

51

E_COMP3_STAT

Elite Compressor #3 Output Status (0=output

 

 

 

 

 

 

 

is OFF, 1=output is ON)

R

(5) BV

52

E_LPS3

Elite Low Pressure Switch for Compressor

 

 

 

 

 

 

 

#3 Input Status (1=closed, 0=open/fault)

R

(5) BV

53

E_HPS3

Elite High Pressure Switch for Compressor

 

 

 

 

 

 

 

#3 Input Status (1=closed, 0=open/fault)

R

(5) BV

54

E_C3_OVRLOAD

Elite Compressor #3 Overload Switch Input

 

 

 

 

 

 

 

Status (1=closed, 0=open/fault)

R

(5) BV

55

E_COMP4_STAT

Elite Compressor #4 Output Status (0=output

 

 

 

 

 

 

 

is OFF, 1=output is ON)

R

(5) BV

56

E_LPS4

Elite Low Pressure Switch for Compressor

 

 

 

 

 

 

 

#4 Input Status (1=closed, 0=open/fault)

R

(5) BV

57

E_HPS4

Elite High Pressure Switch for Compressor

 

 

 

 

 

 

 

#4 Input Status (1=closed, 0=open/fault)

R

(5) BV

58

E_C4_OVRLOAD

Elite Compressor #4 Overload Switch Input

 

 

 

 

 

 

 

Status (1=closed, 0=open/fault)

R

(5) BV

59

E_CFAN2_STAT

Elite Condenser Fan #2 Output Status Input

 

 

 

 

 

 

 

Status (0=output is OFF, 1=output is ON)

R

(5) BV

60

E_GAS_VLVE1

Elite Gas Valve #1 Input Status

 

 

 

 

 

 

 

(1=energized, 0=not energized)

R

(5) BV

61

E_LIMIT_ 1

Elite Limit Switch #1 Input Status (1=closed,

 

 

 

 

 

 

 

0=open/fault)

R

(5) BV

62

E_GAS_VLVE2

Elite Gas Valve #2 Input Status

 

 

 

 

 

 

 

(1=energized, 0=not energized)

R

(5) BV

63

E_LIMIT_ 2

Elite Limit Switch #2 Input Status (1=closed,

 

 

 

 

 

 

 

0=open/fault)

R

(5) BV

64

E_GAS_VLVE3

Elite Gas Valve #3 Input Status

 

 

 

 

 

 

 

(1=energized, 0=not energized)

R

(5) BV

65

E_LIMIT_ 3

Elite Limit Switch #3 Input Status (1=closed,

 

 

 

 

 

 

 

0=open/fault)

R

(5) BV

66

E_FREEZE_ST

Hot H2O Freeze Thermostat Switch #1 Input

 

 

 

 

 

 

 

Status (1=closed, 0=open/fault)

R

(5) BV

67

FAN_HEAT

Turn OFF Continuous Fan when Starting

 

 

 

 

 

 

 

Heat Enabled (0=Continuous Fan ON)

R

(5) BV

68

HEAT_1_STAT

H1 Heating Output #1 Status (0=output is

 

 

 

 

 

 

 

OFF, 1=output is ON)

R

(5) BV

69

HEAT_2_STAT

H2 Heating Output #2 Status (0=output is

 

 

 

 

 

 

 

OFF, 1=output is ON)

R

(5) BV

70

HEAT_3_STAT

H3 Heating Output #3 Status (0=output is

 

 

 

 

 

 

 

OFF, 1=output is ON)

14

Johnson Controls Unitary Products

Page 14
Image 14
Simplicity 514067-UAD-A-0509 manual Descriptor Default Min Max Point Description