TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)

 

BACnet

BACnet

 

 

 

 

 

Read/

Object

Object

 

 

 

 

 

Write

Type

Inst

Descriptor

Default

Min

Max

Point Description

R

(5) BV

44

E_HPS1

Elite High Pressure Switch for Compressor

 

 

 

 

 

 

 

#1 Input Status (1=closed, 0=open/fault)

R

(5) BV

48

E_HPS2

Elite High Pressure Switch for Compressor

 

 

 

 

 

 

 

#2 Input Status (1=closed, 0=open/fault)

R

(5) BV

53

E_HPS3

Elite High Pressure Switch for Compressor

 

 

 

 

 

 

 

#3 Input Status (1=closed, 0=open/fault)

R

(5) BV

57

E_HPS4

Elite High Pressure Switch for Compressor

 

 

 

 

 

 

 

#4 Input Status (1=closed, 0=open/fault)

R

(5) BV

40

E_IFAN_STAT

Elite Indoor Fan Output Status (0=output is

 

 

 

 

 

 

 

OFF, 1=output is ON)

R

(5) BV

61

E_LIMIT_ 1

Elite Limit Switch #1 Input Status (1=closed,

 

 

 

 

 

 

 

0=open/fault)

R

(5) BV

63

E_LIMIT_ 2

Elite Limit Switch #2 Input Status (1=closed,

 

 

 

 

 

 

 

0=open/fault)

R

(5) BV

65

E_LIMIT_ 3

Elite Limit Switch #3 Input Status (1=closed,

 

 

 

 

 

 

 

0=open/fault)

R

(5) BV

43

E_LPS1

Elite Low Pressure Switch for Compressor

 

 

 

 

 

 

 

#1 Input Status (1=closed, 0=open/fault)

R

(5) BV

47

E_LPS2

Elite Low Pressure Switch for Compressor

 

 

 

 

 

 

 

#2 Input Status (1=closed, 0=open/fault)

R

(5) BV

52

E_LPS3

Elite Low Pressure Switch for Compressor

 

 

 

 

 

 

 

#3 Input Status (1=closed, 0=open/fault)

R

(5) BV

56

E_LPS4

Elite Low Pressure Switch for Compressor

 

 

 

 

 

 

 

#4 Input Status (1=closed, 0=open/fault)

R

(2) AV

32

EXH_DAMP_OUT

Exhaust Damper Output Status (0-100%)

R

(5) BV

30

EX_FAN_STAT

Exhaust Fan Output Status (0=output is

 

 

 

 

 

 

 

OFF, 1=output is ON)

R

(5) BV

10

EX_VFD_INST

Exhaust VFD Installed

R

(5) BV

32

FRECOOL_STAT

Free Cooling Mode Status (0=comps not

 

 

 

 

 

 

 

overridden by Econo, 1=comps overridden)

R

(5) BV

68

HEAT_1_STAT

H1 Heating Output #1 Status (0=output is

 

 

 

 

 

 

 

OFF, 1=output is ON)

R

(5) BV

69

HEAT_2_STAT

H2 Heating Output #2 Status (0=output is

 

 

 

 

 

 

 

OFF, 1=output is ON)

R

(5) BV

70

HEAT_3_STAT

H3 Heating Output #3 Status (0=output is

 

 

 

 

 

 

 

OFF, 1=output is ON)

R

(2) AV

76

H1_ACCUM_HRS

Heating #1 Accumulated Run Time

 

 

 

 

 

 

 

(in hours)

R

(2) AV

77

H2_ACCUM_HRS

Heating #2 Accumulated Run Time

 

 

 

 

 

 

 

(in hours)

R

(2) AV

78

H3_ACCUM_HRS

Heating #3 Accumulated Run Time

 

 

 

 

 

 

 

(in hours)

R

(5) BV

25

HEATING_ENA

Heating Mode Enabled

R/W

(2) AV

27

HGR_HUM_STPT

50

0

100

Hot Gas Reheat Humidity Setpoint (percent

 

 

 

 

 

 

 

Humidity)

R

(5) BV

18

HGR_STAT

Hot Gas Reheat Output Status (0=output is

 

 

 

 

 

 

 

OFF, 1=output is ON)

R

(2) AV

47

HGR_VLV_OUT

Hot Gas Reheat Valve Output Status

 

 

 

 

 

 

 

(0-100%)

6