TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED) |
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| BACnet | BACnet |
|
|
|
|
|
|
|
|
|
| Read/ | Object | Object |
|
|
|
|
|
|
|
|
|
| Write | Type | Inst | Descriptor | Default | Min | Max | Point Description |
| |||
| R | (5) BV | 71 | I_IFAN_STAT | – | – | – | |||||
|
|
|
|
|
|
|
| (0=output is OFF, 1=output is ON) |
| |||
| R | (5) BV | 72 | I_FAN_OVER | – | – | – | |||||
|
|
|
|
|
|
|
| Status (0=open,1=closed) |
| |||
| R | (5) BV | 73 | I_COMP1_STAT | – | – | – | |||||
|
|
|
|
|
|
|
| (0=output is OFF, 1=output is ON) |
| |||
| R | (5) BV | 74 | I_LPS1 | – | – | – | |||||
|
|
|
|
|
|
|
| Compressor #1 Input Status (1=closed, | ||||
|
|
|
|
|
|
|
| 0=open/fault) |
| |||
| R | (5) BV | 75 | I_HPS1 | – | – | – | |||||
|
|
|
|
|
|
|
| Compressor #1 Input Status (1=closed, | ||||
|
|
|
|
|
|
|
| 0=open/fault) |
| |||
| R | (5) BV | 76 | I_COMP2_STAT | – | – | – | |||||
|
|
|
|
|
|
|
| (0=output is OFF, 1=output is ON) |
| |||
| R | (5) BV | 77 | I_LPS2 | – | – | – | |||||
|
|
|
|
|
|
|
| Compressor #2 Input Status (1=closed, | ||||
|
|
|
|
|
|
|
| 0=open/fault) |
| |||
| R | (5) BV | 78 | I_HPS2 | – | – | – | |||||
|
|
|
|
|
|
|
| Compressor #2 Input Status (1=closed, | ||||
|
|
|
|
|
|
|
| 0=open/fault) |
| |||
| R | (5) BV | 79 | I_CFAN_STAT | – | – | – | |||||
|
|
|
|
|
|
|
| Status (0=output is OFF, 1=output is ON) |
| |||
| R | (5) BV | 80 | I_GAS_VLVE1 | – | – | – |
| ||||
| R | (5) BV | 81 | I_LIMIT_1 | – | – | – |
| ||||
| R | (5) BV | 82 | I_FREEZE_1 | – | – | – | |||||
|
|
|
|
|
|
|
| Input Status (0=open,1=closed) |
| |||
| R | (5) BV | 83 | I_FREEZE_2 | – | – | – | |||||
|
|
|
|
|
|
|
| Input Status (0=open,1=closed) |
| |||
| R | (5) BV | 85 | ALARM_1_ON | – | – | – | Alarm Buffer #1 (0=Alarm has cleared, | ||||
|
|
|
|
|
|
|
| 1=Alarm is still active) |
| |||
| R | (5) BV | 86 | ALARM_2_ON | – | – | – | Alarm Buffer #2 (0=Alarm has cleared, | ||||
|
|
|
|
|
|
|
| 1=Alarm is still active) |
| |||
| R | (5) BV | 87 | ALARM_3_ON | – | – | – | Alarm Buffer #3 (0=Alarm has cleared, | ||||
|
|
|
|
|
|
|
| 1=Alarm is still active) |
| |||
| R | (5) BV | 88 | ALARM_4_ON | – | – | – | Alarm Buffer #4 (0=Alarm has cleared, | ||||
|
|
|
|
|
|
|
| 1=Alarm is still active) |
| |||
| R | (5) BV | 89 | ALARM_5_ON | – | – | – | Alarm Buffer #5 (0=Alarm has cleared, | ||||
|
|
|
|
|
|
|
| 1=Alarm is still active) |
| |||
| R | (5) BV | 90 | DF_SW_INST | – | – | – | Dirty Filter Switch Installed |
| |||
| R | (5) BV | 93 | OCC_COMS_ENA | – | – | – | Occupied Thermostat or Communication | ||||
|
|
|
|
|
|
|
| Input Enabled |
| |||
| R/W | (5) BV | 96 | MANUAL_WRITE | – | – | – | Manual Write Command to ModlINC |
|
Johnson Controls Unitary Products | 15 |