Simplicity 514067-UAD-A-0509 manual Points List in Object Order

Models: 514067-UAD-A-0509

1 18
Download 18 pages 25.18 Kb
Page 13
Image 13

 

 

 

 

 

 

 

 

514067-UAD-A-0509

 

 

 

 

 

 

 

 

 

 

TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BACnet

BACnet

 

 

 

 

 

 

 

Read/

Object

Object

 

 

 

 

 

 

 

Write

Type

Inst

Descriptor

Default

Min

Max

Point Description

 

 

R

(5) BV

19

LOW_AMB_OVRD

Low Ambient Temperature (0=comps not

 

 

 

 

 

 

 

 

overridden by LAT, 1=comps overridden)

 

 

R

(5) BV

20

POP_ENABLED

Pre-Occupancy Purge Enabled

 

 

R

(5) BV

21

FAN_ON_W_SEN

CV - Indoor Fan Operates with Space

 

 

 

 

 

 

 

 

Sensor Present Option Enabled

 

 

R

(5) BV

22

SAT_COOLING

Supply Air Temperature Limit for Cooling

 

 

 

 

 

 

 

 

Enabled

 

 

R

(5) BV

23

COOLING_ENA

Cooling Mode Enabled

 

 

R

(5) BV

24

SAT_HEATING

Supply Air Temperature Limit for Heating

 

 

 

 

 

 

 

 

Enabled

 

 

R

(5) BV

25

HEATING_ENA

Heating Mode Enabled

 

 

R

(5) BV

26

SEN_FAULT_EN

Space Sensor Fault Override (Construction

 

 

 

 

 

 

 

 

Mode) Enabled

 

 

R

(5) BV

28

INTELLI-STRT

Intelli-Start Enabled

 

 

R

(5) BV

29

BP_SENS_INST

Building Static Pressure Sensor Installed

 

 

R

(5) BV

30

EX_FAN_STAT

Exhaust Fan Output Status (0=output is OFF,

 

 

 

 

 

 

 

 

1=output is ON)

 

 

R

(5) BV

31

ECONO_STATUS

Economizer Output Status (0=not Free

 

 

 

 

 

 

 

 

Cooling, 1= Free Cooling)

 

 

R

(5) BV

32

FRECOOL_STAT

Free Cooling Mode Status (0=comps not

 

 

 

 

 

 

 

 

overridden by Econo, 1=comps overridden)

 

 

R

(5) BV

33

COM_VENT_STA

Comfort Ventilation Mode Status (1=control

 

 

 

 

 

 

 

 

is in Comfort Vent mode, 0= it is not)

 

 

R

(5) BV

34

CVM_COOLING

Comfort Ventilation Mode for Cooling

 

 

 

 

 

 

 

 

Enabled

 

 

R

(5) BV

35

CVM_HEATING

Comfort Ventilation Mode for Heating

 

 

 

 

 

 

 

 

Enabled

 

 

R

(5) BV

36

ECO_L_TO_SAT

Economizer Loading to Control Supply Air

 

 

 

 

 

 

 

 

Temperature Enabled

 

 

R

(5) BV

37

OAH_SENSOR

Outside Air Humidity Sensor Enabled

 

 

R

(5) BV

38

RAH_SENSOR

Return/Inside Air Humidity Sensor Enabled

 

 

R

(5) BV

39

DEMAND_VENT

Demand Ventilation (using Inside Sensor)

 

 

 

 

 

 

 

 

Enabled

 

 

R

(5) BV

40

E_IFAN_STAT

Elite Indoor Fan Output Status (0=output is

 

 

 

 

 

 

 

 

OFF, 1=output is ON)

 

 

R

(5) BV

41

E_FAN_ OVER

Elite Fan Overload Switch Input Status

 

 

 

 

 

 

 

 

(1=closed, 0=open/fault)

 

 

R

(5) BV

42

E_COMP1_STAT

Elite Compressor #1 Output Status (0=output

 

 

 

 

 

 

 

 

is OFF, 1=output is ON)

 

 

R

(5) BV

43

E_LPS1

Elite Low Pressure Switch for Compressor

 

 

 

 

 

 

 

 

#1 Input Status (1=closed, 0=open/fault)

 

 

R

(5) BV

44

E_HPS1

Elite High Pressure Switch for Compressor

 

 

 

 

 

 

 

 

#1 Input Status (1=closed, 0=open/fault)

 

 

R

(5) BV

45

E_C1_OVRLOAD

Elite Compressor #1 Overload Switch Input

 

 

 

 

 

 

 

 

Status (1=closed, 0=open/fault)

 

 

R

(5) BV

46

E_COMP2_STAT

Elite Compressor #2 Output Status (0=output

 

 

 

 

 

 

 

 

is OFF, 1=output is ON)

 

Johnson Controls Unitary Products

13

Page 13
Image 13
Simplicity 514067-UAD-A-0509 manual Points List in Object Order