TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BACnet

BACnet

 

 

 

 

 

 

 

 

Read/

Object

Object

 

 

 

 

 

 

 

 

Write

Type

Inst

Descriptor

Default

Min

Max

Point Description

 

 

 

R/W

(2) AV

71

SPCE_ALM_TMP

0

0

25

Space Sensor Alarm Temperature (degrees

 

 

 

 

 

 

 

 

 

F, 0 = disabled)

 

 

 

R/W

(2) AV

72

SPCE_ALM_TIM

0

0

120

Space Sensor Alarm Time (minutes F, 0 =

 

 

 

 

 

 

 

 

 

disabled)

 

 

 

R

(5) BV

26

SEN_FAULT_EN

Space Sensor Fault Override (Construction

 

 

 

 

 

 

 

 

 

Mode) Enabled

 

 

 

R/W

(2) AV

73

SP_OFF_RANGE

3

0

5

Space Temprature Sensor Offset Range

 

 

 

 

 

 

 

 

 

(0-5 degrees)

 

 

 

R

(2) AV

4

SUP_AIR_TEMP

Supply Air Temperature

 

 

 

R/W

(2) AV

70

SAT_ALM_COOL

0

0

80

Supply Air Temperature Alarm Setpoint for

 

 

 

 

 

 

 

 

 

Cooling

 

 

 

R/W

(2) AV

53

SAT_ALM_HEAT

0

0

120

Supply Air Temperature Alarm Setpoint for

 

 

 

 

 

 

 

 

 

Heating

 

 

 

R

(5) BV

22

SAT_COOLING

Supply Air Temperature Limit for Cooling

 

 

 

 

 

 

 

 

 

Enabled

 

 

 

R/W

(2) AV

3

SAT_COOL_SP

50

40

65

Supply Air Temperature Limit for Cooling

 

 

 

 

 

 

 

 

 

Setpoint (degrees F)

 

 

 

R

(5) BV

24

SAT_HEATING

Supply Air Temperature Limit for Heating

 

 

 

 

 

 

 

 

 

Enabled

 

 

 

R/W

(2) AV

52

SAT_HEAT_SP

135

100

180

Supply Air Temperature Limit for Heating

 

 

 

 

 

 

 

 

 

Setpoint (degrees F)

 

 

 

R

(2) AV

34

SFAN_VFD_OUT

Supply Fan VFD Output Status (0-100%)

 

 

 

R

(2) AV

36

ALARM_1

System Alarm #1

 

 

 

R

(2) AV

37

ALARM_2

System Alarm #2

 

 

 

R

(2) AV

38

ALARM_3

System Alarm #3

 

 

 

R

(2) AV

39

ALARM_4

System Alarm #4

 

 

 

R

(2) AV

40

ALARM_5

System Alarm #5

 

 

 

R/W

(2) AV

29

TH_OFFSET

5

1

10

Temperature/Humidity % Humidity that =

 

 

 

 

 

 

 

 

 

1°F of Offset

 

 

 

R/W

(2) AV

26

TEM_HUM_STPT

50

20

80

Temperature/Humidity Setpoint (percent

 

 

 

 

 

 

 

 

 

Humidity)

 

 

 

R

(5) BV

67

FAN_HEAT

Turn OFF Continuous Fan when Starting

 

 

 

 

 

 

 

 

 

Heat Enabled (0=Continuous Fan ON)

 

 

 

R/W

(2) AV

2

UNOC_COOL_SP

85

45

99

Un-Occupied Cooling Setpoint

 

 

 

R/W

(2) AV

51

UNOC_HEAT_SP

60

45

99

Un-Occupied Heating Setpoint

 

 

 

R/W

(2) AV

75

UNOC_OVR_TP

60

0

240

Unoccupied Override Time Period

 

 

 

R/W

(2) AV

65

VAV_CL_LO_SP

55

40

70

VAV Cooling Supply Air Temperature: Lower

 

 

 

 

 

 

 

 

 

Setpoint (degrees F)

 

 

 

R/W

(2) AV

66

VAV_SAT_RSET

72

40

85

VAV Cooling Supply Air Temperature: Reset

 

 

 

 

 

 

 

 

 

Setpoint (Space Temperature)(degrees F)

 

 

 

R/W

(2) AV

64

VAV_CL_HI_SP

60

40

70

VAV Cooling Supply Air Temperature: Upper

 

 

 

 

 

 

 

 

 

Setpoint (degrees F)

 

 

 

R

(5) BV

5

VAV_OCC_HEAT

VAV Occupied Heating Enabled

 

 

 

R/W

(2) AV

60

VAV_OHEAT_SP

68

40

85

VAV Occupied Heating Setpoint (degrees F)

 