01.2004

Faults and Alarms

 

 

14 Faults and Alarms

14.1Faults

General information about faults

The available information for each fault event comprises the following parameters:

Parameter

r947

Fault number

 

r949

Fault value

 

r951

Fault texts

 

P952

Number of faults

 

r748

Fault time

If a fault message is not acknowledged before the electronics supply voltage is disconnected, then the same fault message will be active again when the supply is next turned on. The drive cannot be started until the message has been acknowledged (exception: Automatic restart function is selected, see P366).

Fault messages

No.

 

 

 

 

Description of fault

 

 

Remedial measures

 

F002

 

Precharging

 

 

 

 

 

 

 

Check the line voltage,

 

 

 

The DC-link voltage failed to reach the minimum limit (

 

 

compare with P071 Line voltage

 

 

 

P071 line supply voltage) during precharging.

 

 

Check the maximum precharging time (P326);

 

 

 

The maximum precharging time (P326) has been

 

 

 

 

 

 

exceeded.

 

 

 

 

 

 

 

 

 

F003

 

Line overvoltage

 

 

 

 

 

Check the line voltage,

 

 

 

The voltage at the input terminals is higher than the

 

 

compare with P071 Line voltage

 

 

 

response threshold (110 % or 120 % of P071 in inverter

 

 

 

 

 

 

disabled or Run states).

 

 

 

 

 

 

 

 

 

The voltage at the input terminals is higher than the

 

 

 

 

 

 

maximum voltage limit + 5 % (E.g.: 460 V + 5 % = 483 V)

 

 

 

 

 

 

and DC-link voltage is higher than the maximum

 

 

 

 

 

 

continuous permissible value.

 

 

 

 

 

 

 

 

 

Line voltage

 

Max. contin. perm. Vd

 

Max. contin. perm. Vd

 

 

 

 

 

 

 

 

 

 

 

 

 

 

range

 

at III >90% P072

 

at III 90% P072

 

 

 

 

 

 

 

380 V to 460 V

 

740 V

 

760 V

 

 

 

 

 

 

 

 

500 V to 575 V

 

922 V

 

947 V

 

 

 

 

 

 

 

660 V to 690 V

 

1100 V

 

1130 V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F004

 

Line undervoltage

 

 

 

 

 

Check the line voltage

 

 

 

The voltage at the input terminals is less than the

 

 

Check P074

 

 

 

response threshold (50 % of P071 during precharging and

 

 

Compare with P071 Line voltage

 

 

 

P074 in operation). The line supply undervoltage fault is

 

 

Check the line phase sequence

 

 

 

also activated if Vsupply < 80 % of P071 and if F013

 

 

 

 

 

occurs.

 

 

 

 

 

 

 

 

 

 

 

If the fault occurs immediately after the drive is started up

 

 

 

 

 

 

(for the first time), then the phase sequence may be

 

 

 

 

 

 

incorrect. The line must always be connected in a CW

 

 

 

 

 

 

phase sequence.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Siemens AG 6SE7087-6CX86-2BA1

14-1

SIMOVERT MASTERDRIVES AFE Operating Instructions

Page 132
Image 132
Siemens 400 V / 210...590 A operating instructions Faults and Alarms, Compare with P071 Line voltage, F003 Line overvoltage