Siemens 400 V / 210...590 A AFE inverter construction type J, Appendix, Masterdrives VC inverters

Models: 400 V / 210...590 A

1 166
Download 166 pages 35.09 Kb
Page 26
Image 26

Installation

01.2004

 

 

5.2.4AFE inverter (construction type J)

Mounting surface

Cutouts for M8 / M10 screw

 

 

 

 

 

 

 

 

H

h

 

Dimen-

Type

Elongated holes

sions

J

9 x 12 construction type J

[mm]

for M8 screws

H

1400

 

 

 

h

1345

 

b

 

b

45

 

 

 

 

550

213

483

708

 

Side view

 

 

800

 

 

 

 

 

 

 

 

Front view

 

 

Fig. 5-6 Mounting dimension, construction type J

NOTE

You can find a full set of dimension sheets for AFE inverters of type J in

 

the appendix.

 

These are identical to the dimension sheets for standard SIMOVERT

 

MASTERDRIVES VC inverters!

 

 

Air cooling

Door/roof openings

 

Explanation of "arcing short-circuit":

 

An underpressure is created in the openings of the cabinet doors due to

 

the flow of air. This is dependent on the volumetric flow and the

 

hydraulic cross-section of the openings.

 

The flow causes a build-up (over) pressure in the roof or in the top

 

cover.

 

As a result of the difference in pressure between the overpressure at

 

the top and the underpressure at the bottom of the cabinet, a flow of air

 

is created inside the unit, a so-called arcing short-circuit. This can be

 

stronger or weaker depending on the volumetric flow and the door/roof

 

opening cross-section.

 

Due to the air flow inside the AFE inverter, preheated air starts to enter

 

the heatsink which causes the equipment to overheat. In addition, a

 

different, more unfavorable operating point is set for the fan.

5-8

6SE7087-6CX86-2BA1 Siemens AG

Operating Instructions SIMOVERT MASTERDRIVES AFE

Page 26
Image 26
Siemens 400 V / 210...590 A operating instructions AFE inverter construction type J, Appendix, Masterdrives VC inverters