Control and Status Words

01.2004

 

 

NOTES

Multiple connections are permitted!

The control word commands "OFF2“ (bit 1), "OFF3“ (bit 2) and "Acknowledge“ (bit 7) are always simultaneously effective from 3 sources (can be parameterized)!

"Acknowledge“ (bit 7) is always additionally effective from the PMU!

If the "ON“ command (bit 0) is connected to a serial interface (SCom, CB/TB, SCB-SCom), then an "OFF2" or "OFF3" command must also be parameterized on the terminal strip. Otherwise, the converter cannot be switched off via a defined command in the event of a communications failure!

13.1.1Display of control word on PMU seven-segment display