01.2004

 

 

 

 

 

 

 

 

 

 

Faults and Alarms

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Alarm messages

 

 

Alarm

 

 

 

Param-

 

 

Description

 

 

 

Remedial measures

 

 

No.

 

 

 

No.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bit No.

 

 

 

 

 

 

 

 

 

 

A039

 

 

 

P955

 

 

Electrical off

 

 

Check

 

 

 

 

 

 

 

 

 

The electronics voltage supply is not o.k.

 

 

the ext. 24 V voltage supply -G1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

 

 

 

 

the digital input and signal lead for monitoring of

 

 

 

 

 

 

 

 

 

 

 

 

 

the ext. 24 V voltage supply

 

 

A040

 

 

 

P955

 

 

Supply voltage

 

 

Check

 

 

 

 

 

 

 

 

 

The voltage at the input terminals is outside the

 

 

the line voltage

 

 

 

 

 

 

 

 

 

rated range (< 80 % or > 110 % of P071) in

 

 

 

 

 

 

7

 

 

 

 

P071 Line voltage

 

 

 

 

 

 

operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A047

 

 

 

P955

 

 

Reactive current limited

 

 

Check the

 

 

 

 

 

 

 

 

 

The reactive current of the AFE is limited.

 

 

line voltage (r030)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

 

 

 

 

 

maximum current (P173)

 

 

 

 

 

 

 

 

 

 

 

 

motor-mode current limit (P160)

 

 

 

 

 

 

 

 

 

 

 

 

generator-mode current limit (P161)

 

 

A048

 

 

 

P955

 

 

Vd2t integrator

 

 

Check the

 

 

 

 

 

 

 

 

 

The monitoring function of the maximum

 

 

line voltage (r030)

 

 

 

 

15

 

 

 

 

 

 

 

 

 

 

continuous DC link voltage (using the Vd2t-

 

 

DC-link voltage (r006)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

integrator) has reached 50 % of the final value. If

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the high DC link voltage is caused by a high

 

 

 

 

 

 

 

 

 

 

 

 

 

 

capacitive reactive current, then this might be

 

 

 

 

 

 

 

 

 

 

 

 

 

 

limited (A047). If the high DC link voltage is caused

 

 

 

 

 

 

 

 

 

 

 

 

 

 

by a high line voltage (r030), the line overvoltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

fault (F003) message will be activated eventually

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(depending on the amplitude of Vd).

 

 

 

 

 

 

 

A049

 

 

 

P956

 

 

No slave

 

 

P660 SCI AnalogInConf

 

 

 

 

 

 

 

On the ser. I/O (SCB1 with SCI1/2), no slave is

 

 

Check slave.

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

connected or fiber optic is interrupted or no supply

 

 

Check fiber optic.

 

 

 

 

 

 

 

 

 

to slaves.

 

 

 

 

 

 

 

A050

 

 

 

P956

 

 

Slave incorrect

 

 

Check P660 SCI AnalogInConf

 

 

 

 

 

 

 

 

 

On the ser. I/O, the slaves connected do not

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

correspond to the parameter setting (slave number

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or slave type).

 

 

 

 

 

 

 

A051

 

 

 

P956

 

 

Peer bdrate

 

 

Match baud rates of SCB boards involved in the

 

 

 

 

 

 

 

Baud rate for peer connection is too high or

 

 

link P684 SCom/SCB Baud

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

different.

 

 

 

 

 

 

 

A052

 

 

 

P956

 

 

Peer PZD-L

 

 

Reduce the number of words

 

 

 

 

 

 

 

PZD length set too high for peer connection (>5).

 

 

P686 SCom/SCB # PrDat..

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A053

 

 

 

P956

 

 

Peer Lng f.

 

 

Match word lengths of sender and receiver

 

 

 

 

 

 

 

The PZD lengths of the sender and receiver in the

 

 

P686 SCom/SCB # PrDat

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

peer connection do not match.

 

 

 

 

 

 

 

A057

 

 

 

P956

 

 

TB-Param

 

 

Replace TB configuration (software).

 

 

 

 

 

 

 

 

 

Alarm occurs if a TB is logged on and connected,

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

but it does not respond to parameter jobs from the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PMU, SCom1 or SCom2 within 6 s.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Siemens AG 6SE7087-6CX86-2BA1

14-7

SIMOVERT MASTERDRIVES AFE Operating Instructions

Page 138
Image 138
Siemens 400 V / 210...590 A operating instructions 14-7