Siemens 400 V / 210...590 A Control transformer must be protected by a 6 a fuse, Mains

Models: 400 V / 210...590 A

1 166
Download 166 pages 35.09 Kb
Page 39
Image 39

Connecting-Up and Wiring

01.2004

 

 

AFE inverter order number /

Input

Mains fuse 3AC

Mains fuse 3AC

rating

current

Utilization category gR

Utilization category gL

 

 

or

 

 

6SE7035-1EJ80 / 340 kW 400 V

510 A

3NE1435-0 560 A

3NA3372 630 A

6SE7036-0EJ80 / 380 kW 400 V

560 A

3NE1436-0 630 A

3NA3372 630 A

 

 

Mains switch

or

No-load fuse-disconnector

 

 

3KL61 30-1AB00 630 A

3NP54 60 - 0CA00 630 A

 

 

24 V power supply 6 A

24 V power supply 10 A

 

 

Unregulated

or

Regulated (SITOP)

 

 

4 AV2295-0AQ00-Z

6EP1-334-2AA00

 

 

 

 

 

 

230 V control transf. 1 kVA

 

 

 

4AM5995-0AH81-0B-Z

 

 

 

 

 

 

Table 7-2 Recommended system components construction type J

NOTE

Owing to the effects of electromagnetic interference, the use of a

 

control transformer to generate the 230 V supply is generally

 

recommended; the fans for AFE inverters can be supplied directly.

 

The control transformer must be protected by a 6 A fuse.

 

 

 

The 24 V power supply can be either regulated or unregulated. This

 

power supply must be protected by a 4 A fuse. It can also be fed in

 

directly from the plant.

 

It is best to use combination fuses (type 3NE1....) for the line-side

 

mains fuses, although miniature circuit-breakers are also allowed.

 

The example configuration (Fig. 7-7) for construction type J shows a

 

switch-disconnector and an EMC filter as a typical configuration for AFE

 

functionality. In this case, the 230 V supply is taken directly from the

 

mains.

 

The same example can also be applied to construction type G.

 

Only difference: The fan connection goes directly to terminals X18.1

 

and X18.5 on the inverter.

7-6

6SE7087-6CX86-2BA1 Siemens AG

Operating Instructions SIMOVERT MASTERDRIVES AFE

Page 39
Image 39
Siemens 400 V / 210...590 A Control transformer must be protected by a 6 a fuse, Directly from the plant, Mains