Control and Status Words

01.2004

 

 

Bit 21: Reserved

Bit 22: Reserved

Bit 23: Reserved

Bit 24: Reserved

Bit 25: Reserved

Bit 26: External fault 2 command (L "External fault 2")

Condition

LOW signal; Command is not activated until converter switches to

 

READY TO RUN (011) and elapse of a 200 ms timer.

Result

♦ FAULT (007) and fault message (F036).

 

The inverter pulses are inhibited and the main contactor (if installed)

 

opened.

 

See Section "Fault and alarm messages".

Bit 27: Slave/master drive command (H "Slave AFE") / (L "Master drive")

Slave AFE

♦ The closed-loop control operates with an external line active current

 

setpoint.

 

The DC link voltage is specified by the master AFE.

Master AFE

♦ The closed-loop control operates with an internal line active current

 

setpoint (= output of DC link voltage controller). The DC link voltage

 

is maintained constantly at the set value.

Bit 28: External alarm 1 command (L "External alarm 1")

Condition

LOW signal

Result

♦ The converter continues to operate in its current status. An alarm

 

message (A015) is output.

 

See Section "Fault and alarm messages".

Bit 29: External alarm 2 command (L "External alarm 2")

Condition

LOW signal

Result

♦ The converter continues to operate in its current status. An alarm

 

message (A016) is output.

 

See Section "Fault and alarm messages".

13-12

6SE7087-6CX86-2BA1 Siemens AG

Operating Instructions SIMOVERT MASTERDRIVES AFE

Page 122
Image 122
Siemens 400 V / 210...590 A operating instructions Master AFE, Bit 28 External alarm 1 command L External alarm Condition