Control and Status Words

01.2004

 

 

Bit 21: Reserved

Bit 22: Reserved

Bit 23: Reserved

Bit 24: Reserved

Bit 25: Reserved

Bit 26: External fault 2 command (L "External fault 2")

Condition

LOW signal; Command is not activated until converter switches to

 

READY TO RUN (011) and elapse of a 200 ms timer.

Result

FAULT (007) and fault message (F036).

 

The inverter pulses are inhibited and the main contactor (if installed)

 

opened.

 

See Section "Fault and alarm messages".

Bit 27: Slave/master drive command (H "Slave AFE") / (L "Master drive")

Slave AFE

The closed-loop control operates with an external line active current

 

setpoint.

 

The DC link voltage is specified by the master AFE.

Master AFE

The closed-loop control operates with an internal line active current

 

setpoint (= output of DC link voltage controller). The DC link voltage

 

is maintained constantly at the set value.

Bit 28: External alarm 1 command (L "External alarm 1")

Condition

LOW signal

Result

The converter continues to operate in its current status. An alarm

 

message (A015) is output.

 

See Section "Fault and alarm messages".

Bit 29: External alarm 2 command (L "External alarm 2")

Condition

LOW signal

Result

The converter continues to operate in its current status. An alarm

 

message (A016) is output.

 

See Section "Fault and alarm messages".

13-12

6SE7087-6CX86-2BA1 Siemens AG

Operating Instructions SIMOVERT MASTERDRIVES AFE

Page 122
Image 122