Siemens 400 V / 210...590 A 12-11, P160 Startmot,max, P161 Startgen,max, P164 Operating mode

Models: 400 V / 210...590 A

1 166
Download 166 pages 35.09 Kb
Page 81
Image 81

 

01.2004

 

 

 

 

 

 

Parameter List

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PNU

 

Parameter Name in OP1

 

 

Range

# of Indices

read:

_/_

 

 

 

 

 

 

 

 

[Unit]

Factory

write:

_/_

 

 

*:conf-P

 

Description

 

 

 

Value Texts

Settings

 

 

 

 

 

P155

 

max. t. pow.fail

 

 

0 to 3000

3 /

BR

 

 

 

 

 

 

Maximum time until the power failure fault (F009) or line supply

 

[ms]

100

3 /

BR

 

 

 

9BHex

 

undervoltage fault (F004) is output.

 

 

 

 

 

 

 

 

 

 

If the unsmoothed line supply voltage falls below the threshold

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

parameterized in P074, the inverter firing pulses are inhibited.

 

 

 

 

 

 

 

 

 

 

 

The main contactor remains closed. If the line supply voltage

 

 

 

 

 

 

 

 

 

 

 

does not increase above the minimum threshold (P074) within

 

 

 

 

 

 

 

 

 

 

 

the maximum time for a power failure, the power failure fault

 

 

 

 

 

 

 

 

 

 

 

F009 is output and the main contactor is opened (de-

 

 

 

 

 

 

 

 

 

 

 

energized).

 

 

 

 

 

 

 

 

 

 

 

 

 

If the smoothed line supply voltage falls below the threshold

 

 

 

 

 

 

 

 

 

 

 

parameterized in P074, fault message F004 "line supply

 

 

 

 

 

 

 

 

 

 

 

undervoltage" is output.

 

 

 

 

 

 

 

 

 

 

 

 

Type=O2;

PKW: 1HEX=1 s

ZD-Gr.: 0

 

 

 

 

 

 

 

 

P160

 

I start(mot,max)

 

 

0.0 to 150.0

2

3 /

ABR

 

 

 

 

Maximum current limit for motor operation.

 

[%]

i001=150.0

3 /

A

 

 

 

A0Hex

 

The line current is limited by this parameter.

 

 

i002=150.0

 

 

 

 

 

 

 

 

RDS(2) parameter

 

 

 

 

 

 

 

 

 

 

 

 

Type=I2;

PKW: 1HEX=0.1 %

PZD: 4000HEX = 400 %

 

 

 

 

 

 

 

 

P161

 

I start(gen,max)

 

 

150.0 to 0.0

2

3 /

ABR

 

 

 

 

Maximum regenerative current limit.

 

 

[%]

i001=-150.0

3 /

A

 

 

 

A1Hex

 

The regenerative feedback current is limited to the value set

 

 

i002=-150.0

 

 

 

 

 

 

 

 

here..0

 

 

 

 

 

 

 

 

 

 

 

 

 

RDS(2) parameter

 

 

 

 

 

 

 

 

 

 

 

 

Type=I2;

PKW: 1HEX=0.1 %

PZD: 4000HEX = 400 %

 

 

 

 

 

 

 

 

 

P164

 

Operating mode

 

 

0 to 2

2

3 / ABR

 

 

 

 

A4Hex

 

Selection of the operating mode

 

 

 

i001=1

3 /

A

 

 

 

 

 

Parameter values:

 

 

 

i002=1

 

 

 

 

 

 

 

 

0: Operating mode “reactive power compensation”

 

 

 

 

 

 

 

 

 

 

 

The setpoint for the reactive power can be set via P122.

 

 

 

 

 

 

 

 

 

 

 

1: Operating mode "cos(PHI)"

 

 

 

 

 

 

 

 

 

 

 

 

The setpoint for the cos(PHI) can be set via P120.

 

 

 

 

 

 

 

 

 

 

 

2: Operating mode "closed-loop current control"

 

 

 

 

 

 

 

 

 

 

 

The source of the current setpoint must be entered via

 

 

 

 

 

 

 

 

 

 

 

P486.

 

 

 

 

 

 

 

 

 

 

 

 

 

3: Regenerative partial load

 

 

 

 

 

 

 

 

 

 

 

 

RDS(2) parameter

 

 

 

 

 

 

 

 

 

 

 

 

Type=O2;

PKW: 1HEX=1

PZD Gr.:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Siemens AG 6SE7087-6CX86-2BA1

12-11

SIMOVERT MASTERDRIVES AFE Operating Instructions

Page 81
Image 81
Siemens 400 V / 210...590 A operating instructions 12-11, P160 Startmot,max, P161 Startgen,max, P164 Operating mode