Siemens 400 V / 210...590 A operating instructions 12-36, R949 Fault Value, R951 Fault Texts

Models: 400 V / 210...590 A

1 166
Download 166 pages 35.09 Kb
Page 106
Image 106

 

 

Parameter List

 

 

 

 

 

 

 

01.2004

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PNU

 

Parameter Name in OP1

 

 

 

 

Range

 

# of Indices

 

read:

_/_

 

 

 

 

 

 

 

 

 

[Unit]

 

Factory

 

write:

_/_

 

 

*:conf-P

 

Description

 

 

 

 

Value Texts

 

Settings

 

 

 

 

 

 

r947

 

Fault Memory

 

 

 

 

 

64

 

2 / BR

 

 

 

 

3B3Hex

 

Display of faults which caused the last 8 fault events (r748); up

 

 

 

 

 

 

 

 

 

to 8 faults can be stored for each event. Each fault has its own

 

 

 

 

 

 

 

 

 

 

fault number (see list of faults, Section 7). For plain text

 

 

 

 

 

 

 

 

 

 

 

 

 

information associated with fault numbers: See r951.

 

 

 

 

 

 

 

 

 

 

 

 

 

Indices:

Fault 1

Fault 2

...

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fault 8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Latest fault (1)

i001=S1-1

i002=S1-2 ...

 

 

 

 

 

 

 

 

 

 

 

i008=S1-8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Last acknowledged fault (2)

i009=S2-1

i010=S2-2 ...

 

 

 

 

 

 

 

 

 

 

 

i016=S2-8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2nd last acknowledged fault (3)

i017=S3-1

i018=S3-2 ...

 

 

 

 

 

 

 

 

 

...

i024=S3-8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Oldest fault stored (8)

i057=S8-1

i058=S8-2 ...

 

 

 

 

 

 

 

 

 

 

 

i064=S8-8

 

 

 

 

 

 

 

 

 

 

Notes: A value of "0" means "No fault".

In the event of a power failure, only the current and last acknowledged fault are stored. Indices 17 to 64 are then reset to 0. See P952 for the number of stored fault events.

Example of a fault:

Last acknowledged fault (2)

Index

r947

 

r949

Index

r748

 

 

 

 

 

 

9

35

 

0

4

62

10

37

 

2

5

1

11

0

 

0

6

7

12

 

 

 

 

 

13

 

 

 

 

 

14

 

 

 

 

 

15

 

 

 

 

 

16

 

 

 

 

 

Fault time (r748): after 62 days, 1 hour, 7 sec operating hours

Faults occurrences (r947): Fault value (r949):

35No further details

372

 

Type=O2;

PKW: 1HEX=1.0

PZD Gr.: 0

 

 

r949

Fault Value

 

64

3 /

BR

 

Fault value of faults, facilitates troubleshooting for a variety of

 

 

3B5Hex

parameters.

 

 

 

 

 

The fault values are stored in the same indices as the

 

 

 

associated fault numbers (r947) - see example in r947.

 

 

 

Type=O2;

PKW: 1HEX=1.0

PZD Gr.: 0

 

 

 

 

 

 

 

 

r951

Fault Texts

 

116

2 /

BR

 

List of fault texts; every fault text is stored under the same index

 

 

3B7Hex

as its fault number.

 

 

 

 

Example (cf. r947): Fault 35 is stored in r947, i009.

 

 

 

 

This is (r951, i035): 'Ext.fault1'.

 

 

 

Type=O2;

PKW: 1HEX=1.0

PZD Gr.: 0

 

 

12-36

6SE7087-6CX86-2BA1 Siemens AG

Operating Instructions SIMOVERT MASTERDRIVES AFE

Page 106
Image 106
Siemens 400 V / 210...590 A operating instructions 12-36, R949 Fault Value, R951 Fault Texts