Basic Function Check

01.2004

 

 

Preliminary check

Activating main switch -Q1

Parameter reset

Main contactor -K1 and precharging contactor -K4 must be open

Main switch must be open

Mains voltage must be applied to the main switch

Ensure clockwise rotating field

Control panel (PMU) must still be dark

Control transformer -T10 must be wired

Fuses must be connected

Control transformer -T10 supplies 230 V AC

to the fan of the AFE inverter

to the DC power supply -G10

to the switching contact for the precharging contactor X9: 4: 230 V,

X9: 5 to the -X70.1 of the CleanPower filter

24 V power supply -G10 to the AFE inverter

-X9: 1 (P24) 2:(M24) and to VSB -X3: pins 3 and 2 (ground)

On the AFE inverter, the control panel (PMU) lights up, initialization has been completed after several seconds and the status message: 0009 = READY FOR ON appears on the PMU.

If the READY FOR ON message does not appear, check all contacts, fuses and voltages once again and replace CUSA if necessary.

P052 = 1

Reset is run

P052 automatically returns to 0.

Disabling control of

P561 = 0

the AFE inverter

 

CAUTION

 

If this is not observed, the fuse may blow or the Clean Power filter

 

may be subjected to increased stress!

 

 

8-2

6SE7087-6CX86-2BA1 Siemens AG

Operating Instructions SIMOVERT MASTERDRIVES AFE

Page 54
Image 54
Siemens 400 V / 210...590 A operating instructions P052 =, Reset is run P052 automatically returns to