Control and Status Words

 

 

Bit #

Value

1 = High

Select

 

 

0 = Low

destin.

 

Value

Destination

Bit 16

 

Reserved

 

Bit 17

 

Reserved

 

Bit 18 2)

1

Current limit active

P618.x

 

0

Current limit not active

 

Bit 19

1

External fault 1

P619.x

 

0

No external fault 1

 

Bit 20

1

External fault 2

P620.x

 

0

No external fault 2

 

Bit 21

1

External alarm

P621.x

 

0

No external alarm

 

Bit 22

1

AFE i2t alarm

P622.x

 

0

No AFE i2t alarm

 

Bit 23

1

AFE overtemp. fault

P623.x

 

0

No AFE overtemp. fault

 

Bit 24

1

AFE overtemp. alarm

P624.x

 

0

No AFE overtemp. alarm

 

Bit 25

 

Reserved

 

Bit 26

 

Reserved

 

Bit 27

 

Reserved

 

Bit 28

 

Reserved

 

Bit 29 3)

1

PC contactor energized

P629.x

 

0

PC cntact. not energized

 

Bit 30

 

Reserved

 

Bit 31

1

Precharging active

P631.x

 

0

Precharging not active

 

x = 1 0000 1001 1002 1003 1004

0000

4101

4102

4103

4104

4105

4106

4107

4108

4109 x = 2 4110 4111 4112 4201 4202 4203 4204 4205 4206 4207 4208 4209 4210 4211 4212

No destination

Assigned

Assigned

BA3, -X102:29/33

BA4, -X102:32/33

No destination

SCI 1/2, slave 1, BA1

SCI 1/2, slave 1, BA2

SCI 1/2, slave 1, BA3

SCI 1/2, slave 1, BA4

SCI 1/2, slave 1, BA5

SCI 1/2, slave 1, BA6

SCI 1/2, slave 1, BA7

SCI 1/2, slave 1, BA8

SCI 2 only, slave 1, BA9

SCI 2 only, slave 1, BA10

SCI 2 only, slave 1, BA11

SCI 2 only, slave 1, BA12

SCI 1/2, slave 2, BA1

SCI 1/2, slave 2, BA2

SCI 1/2, slave 2, BA3

SCI 1/2, slave 2, BA4

SCI 1/2, slave 2, BA5

SCI 1/2, slave 2, BA6

SCI 1/2, Slave 2, BA7

SCI 1/2, Slave 2, BA8

SCI 2 only, Slave 2, BA9

SCI 2 only, Slave 2, BA10

SCI 2 only, Slave 2, BA11

SCI 2 only, Slave 2, BA12

x = 3 0000

No destination

 

 

 

 

 

 

5001

TSY, BA1

 

 

 

 

 

5002

TSY, BA2

 

 

 

 

2)This bit corresponds to "Overspeed" bit on the MASTERDRIVES CUVC

3)This bit corresponds to "Bypassing contactor energized" bit on the MASTERDRIVES CUVC

Siemens AG 6SE7087-6CX86-2BA1

13-17

SIMOVERT MASTERDRIVES AFE Operating Instructions

Page 127