Siemens 400 V / 210...590 A Functions, P387, P408 Forming time, P409 Line contac. del

Models: 400 V / 210...590 A

1 166
Download 166 pages 35.09 Kb
Page 84
Image 84

Parameter List

01.2004

 

 

12.6Functions

PNU

 

Parameter Name in OP1

 

Range

# of Indices

read:

_/_

 

 

 

 

 

[Unit]

Factory

write:

_/_

*:conf-P

 

Description

 

 

Value Texts

Settings

 

 

 

P366

 

Auto Restart

 

 

0 to 2

2

3 /

BR

 

 

 

Automatic restart (WEA) after power failure

 

i001=0

3 /

BR

 

16EHex

 

Parameter values:

 

 

i002=0

 

 

 

 

 

0 = Inhibited

 

 

 

 

 

 

 

 

1 = Power failure acknowledgement only after power

 

 

 

 

 

 

 

recovery

 

 

 

 

 

 

 

 

2 = AFE is restarted after power recovery

 

 

 

 

 

 

 

CAUTION:

External safety devices must be provided to

 

 

 

 

 

 

 

 

ensure that the AFE does not start accidentally

 

 

 

 

 

 

 

 

when P366 = 2!

 

 

 

 

 

 

 

 

RDS(2) parameter

 

 

 

 

 

 

 

 

Type=O2;

PKW: 1HEX=1

PZD Gr.: -

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P387

 

Vd minimum

 

 

5 to 140

3 /

BR

 

 

 

Response threshold for shutdown

 

[%]

100

3 /

BR

 

183Hex

 

DC-link undervoltage in closed-loop current control mode

 

 

 

 

 

 

 

(P164 = 2). The line supply voltage is the reference quantity

 

 

 

 

 

 

 

(P071).

 

 

 

 

 

 

 

 

 

Type=O2;

PKW: 1HEX=1 %

PZD Gr.:

 

 

 

 

 

P408

 

Forming time

 

1.0 to 600.0

2

2 / ABR

 

 

 

DC link forming time

 

[min]

i001=10.0

2 /

AB

 

198Hex

 

This parameter defines the forming period for the DC link when

 

i002=10.0

 

 

 

 

 

P052=20.

 

 

 

 

 

 

 

 

 

RDS parameter

 

 

 

 

 

 

 

 

Type=O2;

PKW: 1HEX=0.1 min

PZD Gr.: 0

 

 

 

 

 

P409

 

Line contac. del.

 

0.0 to 6.5

3 /

BR

 

199Hex

 

Delay time for commencement of precharging process.

[s]

0.0

3 /

B

 

 

This parameter can be used to implement a time-graded

 

 

 

 

 

 

 

sequence for starting up a number of drive units.

 

 

 

 

 

 

 

Type=O2;

PKW: 1HEX=0.1 s

PZD Gr.:

 

 

 

 

 

12-14

6SE7087-6CX86-2BA1 Siemens AG

Operating Instructions SIMOVERT MASTERDRIVES AFE

Page 84