Siemens 400 V / 210...590 A operating instructions 17-3

Models: 400 V / 210...590 A

1 166
Download 166 pages 35.09 Kb
Page 151
Image 151

01.2004Technical Data

Supply system type

TN-C; 3/PEN

 

 

 

Mains voltage

3AC 400 V

 

 

 

Mains frequency

50 Hz / 60 Hz

 

 

 

Rated operating voltage

3 AC 380 (-20 %) V to 3AC 460 (+5 %) V)

Rated current

210 A, 260 A, 315 A, 370 A, 510...590 A

Power loss

CleanPower filter

Approx. 300 Watt (construction type G)

 

 

 

Approx. 500 Watt (construction type J)

 

AFE basic mains module

Negligible

 

AFE reactor

 

See below

Control voltage / auxiliary supply

DC24, AC230 V

 

 

Incoming fuse

See operating manual for AFE chassis units

Short-circuit strength

Depends on incoming fuse

 

 

Protection class to EN50178

I

 

 

 

Protective measures

Cover with optionally large surface against direct contact,

 

as chassis unit by enclosure to DIN EN 60204-1

 

in case of indirect contact automatic disconnection by overcurrent

 

protective device in the TN system

Operating mode

Continuous operation

 

 

Inputs/outputs

Mains incoming feeder at contactor K1

 

Mains outgoing feeder to AFE reactor at reactor terminals of line

 

commutating reactor via cable lug M12 or conductor bar

Table 17-2

Electrical technical data

 

 

 

 

 

 

Dimensions

CleanPower filter

 

 

 

Mounting space:

 

 

 

W: 502 mm

H: 700 mm

 

D: 377 mm

 

Maximum mounting dimensions with clearance for connections

 

W: 510 mm

H: 1300 mm

 

D: 380 mm

 

AFE basic mains module

 

 

 

Mounting space:

 

 

 

W: 342 mm

H: 700 mm

 

D: 377 mm

Weight

AFE basic mains module

 

16 kg

 

CleanPower filter (210...590 A)

44 kg ... 78 kg

 

(ready assembled:

 

60 kg ... 94 kg)

Surface

Housing sendzimized

 

 

 

 

 

Tank

Mounting plate special housing

 

 

 

 

 

Table 17-3

Mechanical technical data

 

 

The machine control is manufactured in accordance with DIN EN 60439-1, also taking into account DIN EN 60204-1. In the delivery state, the protection against indirect contact for the machine control is afforded by automatic disconnection in the TN system. If protection against indirect contact with the equipment is to be afforded by a different system, the circuit configuration must be adapted accordingly.

DIN EN 60204-1 specifies that only electricians and/or other personnel with proper training in handling electrical circuitry may have access to the internal components of the electrical system.

Siemens AG 6SE7087-6CX86-2BA1

17-3

SIMOVERT MASTERDRIVES AFE Operating Instructions