Connecting-Up and Wiring

01.2004

 

 

7.2Power connections

NOTE

The connection cross-sections are determined for copper cables at

 

40

°C (104 °F) ambient temperature (according to DIN VDE 0298 Part

 

4 /

02.88 Group 5).

7.2.1AFE inverter and AFE reactor

The supply terminals are marked as follows:

Motor-end inverter:

C/L+

D/L-

 

AFE reactor connection:

U2/T1

V2/T2

W2/T3

PE conductor connection:

PE1

PE2

 

Mains voltage 380 V to 460 V

Order numbers

Rated output

Rated input

Reactor

Output end DC

 

 

 

 

current

connection to

DC link connection

 

 

 

 

AFE inverter -X2

AFE reactor

AFE-Inverter

 

3 ph. AC

 

 

Rated output

 

 

 

 

 

mains end

Cross section

current

Cross section

Position 1

Position 2

 

 

VDE

Max.

 

VDE

Max.

6SE70...

6SE70...

 

[A]

[mm2]

 

[A]

[mm2]

 

36-0ES87-1FG1

35-1EJ80

340 kW / 400 V

510

2x185

2x300

570

2X185

4x300

36-0ES87-1FG1

36-0EJ80

380 kW / 400 V

560

2x240

4x300

630

2x240

4x300

33-7ES87-1FG1

33-7EJ80

250 kW / 400 V

370

2x120

2x150

425

2x120

2x150

33-2ES87-1FG1

33-2EJ80

214 kW / 400 V

315

2x95

2x150

360

2x120

2x150

32-6ES87-1FG1

32-6EJ80

177 kW / 400 V

260

2x70

2x150

300

2x95

2x150

32-1ES87-1FG1

32-1EJ80

143 kW / 400 V

210

2x50

2x150

240

2x70

2x150

Table 7-3 Conductor cross-sections AFE inverter

NOTE

The mechanical construction must provide the earth connection for the

 

AFE reactor (baseplate connection). The terminal links must be

 

protected against accidental contact.

7-8

6SE7087-6CX86-2BA1 Siemens AG

Operating Instructions SIMOVERT MASTERDRIVES AFE

Page 41