01.2004

Parameter List

 

 

12.7Setpoint channel

 

PNU

 

 

Parameter Name in OP1

 

 

Range

# of Indices

read:

_/_

 

 

 

 

 

 

 

 

[Unit]

Factory

write:

_/_

 

*:conf-P

 

 

Description

 

 

Value Texts

Settings

 

 

 

 

P443

 

 

Src. Ud (set)

 

 

0 to 4545

2

3 /

BR

 

 

*

 

 

Source for the DC-link voltage setpoint.

 

 

i001=1001

3 /

BR

 

 

1BBHex

 

 

Parameter values:

 

 

 

i002=1001

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1001:

Fixed setpoint

 

 

 

 

 

 

 

 

 

 

 

Other values: Acc. to process data connections of setpoint

 

 

 

 

 

 

 

 

 

 

channel.

 

 

 

 

 

 

 

 

 

 

 

B/R parameter

 

 

 

 

 

 

 

 

 

 

 

Type=L2;

PKW format(HEX)=param.value

PZD Gr.: 0

 

 

 

 

 

 

P444

 

 

Vd (set) Kp

 

 

0.0 to 300.0

2

3 /

BR

 

 

1BCHex

 

 

Gain for the DC-link voltage setpoint.

 

 

[%]

i001=100.0

3 /

BR

 

 

 

 

B/R parameter

 

 

 

i002=100.0

 

 

 

 

 

 

 

Type=I2;

PKW: 1HEX=0.1 %

PZD: 4000HEX = 400 %

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

r447

 

 

Vd (set,source)

 

 

 

3 /

BR

 

 

1BFHex

 

 

Setpoint of DC-link voltage from setpoint nodes.

 

[V]

 

 

 

 

 

 

 

The Vd setpoint is always limited to sensible values so as to

 

 

 

 

 

 

 

 

 

prevent shutdown on faults as a result of impermissibly high

 

 

 

 

 

 

 

 

 

setpoints.

 

 

 

 

 

 

 

 

 

 

 

 

Minimum value: Peak value of line voltage = 1.42 x r030

 

 

 

 

 

 

 

 

 

Maximum value: 2x rated line voltage = 2 x P071

 

 

 

 

 

 

 

 

 

 

Analog output: 100 % with code number (PWE) = 4*P071

 

 

 

 

 

 

 

 

 

Type=O2;

PKW: 1HEX=1 V

PZD Gr.: 7

 

 

 

 

 

 

 

P486

 

 

Src.curr.setp.

 

 

0 to 4545

2

3 /

BR

 

 

*

 

 

Source for the setpoint of the active (line) current

 

 

i001=0

3 /

BR

 

 

1E6Hex

 

 

The parameterized active current setpoint is effective only in

 

i002=0

 

 

 

 

 

 

 

"Closed-loop current control" (P164 = 2) or "Slave AFE"

 

 

 

 

 

 

 

 

 

modes (CW2, bit 27).

 

 

 

 

 

 

 

 

 

 

 

Parameter values acc. to process data connections of setpoint

 

 

 

 

 

 

 

 

 

channel.

 

 

 

 

 

 

 

 

 

 

 

 

B/R parameter

 

 

 

 

 

 

 

 

 

 

 

Type=L2;

PKW format(HEX)=param. value

PZD Gr.: 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P487

 

 

Curr.setp. Kp

 

 

300.0 to 300.0

2

3 /

BR

 

 

 

 

 

Gain for the setpoint of the active (line) current in "Closed-loop

[%]

i001=100.0

3 /

BR

 

 

1E7Hex

 

 

current control" (P164 = 2) or "Slave AFE" modes (CW2, bit

 

i002=100.0

 

 

 

 

 

 

27).

 

 

 

 

 

 

 

 

 

 

 

 

B/R parameter

 

 

 

 

 

 

 

 

 

 

 

Type=I2;

PKW: 1HEX=0.1 %

PZD: 4000HEX = 400 %

 

 

 

 

 

 

r490

 

 

Curr.setp.

 

 

 

3 /

BR

 

 

1EAHex

 

 

Active (line) current setpoint in "Closed-loop current control"

[A]

 

 

 

 

 

 

 

(P164 = 2) or "Slave AFE" modes (CW2, bit 27).

 

 

 

 

 

 

 

 

 

 

Analog output: 100 % with code number (PWE) = 400 %

 

 

 

 

 

 

 

 

 

Type=I2;

PKW: 1HEX=0.1 %

PZD: 4000HEX = 400 %

 

 

 

 

 

Siemens AG 6SE7087-6CX86-2BA1

12-15

SIMOVERT MASTERDRIVES AFE Operating Instructions

Page 85
Image 85
Siemens 400 V / 210...590 A operating instructions Setpoint channel