01.2004

 

 

 

 

 

 

 

Parameter List

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PNU

 

Parameter Name in OP1

 

 

Range

# of Indices

read:

_/_

 

 

 

 

 

 

 

 

[Unit]

Factory

write:

_/_

 

*:conf-P

 

Description

 

 

 

Value Texts

Settings

 

 

 

 

 

P569

 

Src Jog2 ON

 

 

 

0 to 5001

2

2 /

BR

 

 

 

*

 

Source for the Inching 2 setpoint (control word 1, bit 8)

 

i001=0

2 /

BR

 

 

 

239Hex

 

See Section "Control word" for details

 

 

i002=0

 

 

 

 

 

 

 

Parameter values: 0:

No inching

 

 

 

 

 

 

 

 

 

 

 

 

1:

Illegal setting

 

 

 

 

 

 

 

 

 

 

 

 

2001: SST1, word 1, bit 8

 

 

 

 

 

 

 

 

 

 

Other values:

See permissible settings in Section "Control

 

 

 

 

 

 

 

 

 

 

 

word"

 

 

 

 

 

 

 

 

 

 

 

B/R parameter

(process data connections of control word)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type=L2;

PKW format(HEX)=param.value

PZD Gr.: 0

 

 

 

 

 

 

 

P572

 

Src.regen.enable

 

 

 

0 to 5001

2

2 /

BR

 

 

 

*

 

Source for control command "Regenerative feedback enabled"

 

i001=1

2 /

BR

 

 

 

23CHex

 

(control word 1, bit 12)

 

 

 

i002=1

 

 

 

 

 

 

 

Parameter values: 0:

Regenerative feedback disabled

 

 

 

 

 

 

 

 

 

 

 

1:

Regenerative feedback enabled

 

 

 

 

 

 

 

 

 

 

 

2001: SST1, word 1, bit 8

 

 

 

 

 

 

 

 

 

 

Other values:

See permissible settings in Section "Control

 

 

 

 

 

 

 

 

 

 

 

word"

 

 

 

 

 

 

 

 

 

 

 

B/R parameter

(process data connections of control word)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type=L2;

PKW format(HEX)=param.value

PZD Gr.: 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P575

 

Src No Ext Fault1

 

 

 

1 to 5001

2

2 /

BR

 

 

 

*

 

Source for control command "External fault 1" (control word 1,

 

i001=1

2 /

BR

 

 

 

23FHex

 

bit 15)

 

 

 

 

 

i002=1

 

 

 

 

 

 

 

An L signal causes the drive to shut down on faults.

 

 

 

 

 

 

 

 

 

Parameter values: 0:

Illegal setting

 

 

 

 

 

 

 

 

 

 

 

 

1:

No fault

 

 

 

 

 

 

 

 

 

 

 

 

1001: CUSA digital input 1

 

 

 

 

 

 

 

 

 

 

Other values:

See permissible settings in Section "Control

 

 

 

 

 

 

 

 

 

 

 

word"

 

 

 

 

 

 

 

 

 

 

 

B/R parameter

(process data connections of control word)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type=L2; PKW: PKW format(HEX)=param.value

PZD Gr.: 0

 

 

 

 

 

 

 

P576

 

Src. ext. 24V ok

 

 

 

0 to 5001

2

3 /

BR

 

 

 

*

 

Source for the bit for monitoring the external 24 V power

 

i001=1004

3 /

BR

 

 

 

240Hex

 

supply.

 

 

 

 

 

i002=1004

 

 

 

 

 

 

 

This bit is connected to digital input 4 on the CUSA at the

 

 

 

 

 

 

 

 

 

factory.

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter values: 0:

Ext. 24V not o.k.

 

 

 

 

 

 

 

 

 

 

 

 

1:

Ext. 24V o.k.

 

 

 

 

 

 

 

 

 

 

 

 

1001: CUSA digital input 1

 

 

 

 

 

 

 

 

 

 

Other values:

See permissible settings in Section "Control

 

 

 

 

 

 

 

 

 

 

 

word"

 

 

 

 

 

 

 

 

 

 

 

B/R parameter

(process data connections of control word)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Type=L2;PKW format(HEX)=param.value

PZD Gr.: 0

 

 

 

 

 

 

Siemens AG 6SE7087-6CX86-2BA1

12-19

SIMOVERT MASTERDRIVES AFE Operating Instructions

Page 89
Image 89
Siemens 400 V / 210...590 A operating instructions 12-19, P572, P575 Src No Ext Fault1, P576 Src. ext V ok